ABB MNS iS System Setup & Operation Quick Guide / System Release 6.0 – Rev.2 / Aug. 2011
6
6
7
7
Relates to
Message
Motor Starter System
Alarm condition Trip condition
Operating Hours X
Number of motor operating
hours has exceeded the
parameterized Alarm level
Suggested action:
Module maintenance
Note:
To reset the Alarm
message:
increase the parameter
value
Download Parameter to
MControl
n.a.
Insertion Cycle
Supervision MStart
X
Number of Power Module
insertion cycles is higher
than parameterized Alarm
level
Suggested action:
Power Module
maintenance
Check MNS Service
Manual for details
n.a.
IRF Hardware
(alternative 1)
NOTE:
This message is
generated due to
internal hardware
house keeping
tasks within the
MNS iS System
X n.a.
Incorrect Application
Download
Should an application be
utilized requiring an
Extended I/O card, AIAO,
PTC, DI/DO and that
application downloaded to
an MControl without the
extended I/O card present,
the MControl will issue the
IRF Hardware Trip.
Suggested action:
Ensure that the correct
firmware application and
the correct MControl
hardware are utilised.

Table of Contents