Section 3 Location of interface ports and LED‘s
Connection to console port
The console port can be used to connect to the CLI (Command Line Interface).
The following steps needs to be taken:
1. Connect the serial diagnostic cable to the console port (use only ABB cable
3BSE080212R1).
2. Connect cable to your computer (USB port, if drivers are needed they can be
downloaded from our Web page).
3. Use a terminal emulator and connect with correct speed and format (115200,
8N1) to the assigned port.
For more information about the CLI, see the NEOS User Manual.
Power connection
Figure 2. Power Connection
NE810 supports redundant power connection. The positive inputs are +DC1 and
+DC2, the negative input for both supplies are –COM. Connect the primary voltage
(e.g. +24 VDC) to the +DC1 pin and return to one of the –COM pins on the power
input.
3BSE080633 13
4-position Product marking Direction Description
No. 1 +DC1 Input Supply voltage input DC1
No. 2 +DC2 Input Supply voltage input DC2
No. 3 -COM Input Common
No. 4 -COM Input Common