EasyManuals Logo

ABB OTM C 21D User Manual

ABB OTM C 21D
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
22
AUTOMATIC TRANSFER SWITCH, OTM_C_21D
Automatic transfer switch Parameters
Rated operational voltage Ue[V]
Single-phase (2P)
Three-phase (3P/4P)
220~240 V AC 50~60 Hz
380/400/415
Frequency 50Hz/60 Hz
Operating voltage range 0.7~1.3 Ue
Measuring accuracy ±3%
Operating angle 90° ( O-I, I-O, O-II, II-O)
180° ( I-O-II, II-O-I)
OFF time 0,6 - 0,7 s
Total transfer time 2.5 s
Output relay utilization category 3A, AC1, 250V
Electromagnetic compatibility Class B
Ingress Protection Rating IP20, front panel
Rated impulse withstand voltage Uimp 8 kV (6 kV for control circuit, disconnect the power line of
the control circuit before carrying out the dielectric voltage
withstand test)
Operating temperature -25~55C
Transportation and storage temperature -40~70C
Altitude Max. 2000 m
5. Technical data
Table 9. Technical data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB OTM C 21D and is the answer not in the manual?

ABB OTM C 21D Specifications

General IconGeneral
BrandABB
ModelOTM C 21D
CategorySwitch
LanguageEnglish

Related product manuals