EasyManua.ls Logo

ABB PM571 - 4. Appendix; 4.1 Technical Data

ABB PM571
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
________________________________________________________________________________________________________
AC500-eCo - 19 -
Hardware Introduction
4. Appendix
4.1 Technical Data
CPU
PM554 PM564
Table 0, Details/Type
PM554-T, PM554-R PM554-R-AC PM564-T, PM564-R
Supply voltage 24 V DC 24V DC or 100-240V AC 24 V DC
Program memory 128 KB 128 KB 128 KB
Integrated data memory[KB] 10 KB 10 KB 10 KB
Memory card adapter (option)
Plug-in memory card [SD card] 512MB 512MB 512MB
for storage user data
x x x
for storage program
x x x
for update firmware
x x x
Cycle time for 1000 instruction in ms
binary 0.3 ms 0.3 ms 0.3 ms
word 0.3 ms 0.3 ms 0.3 ms
floating 6.0 ms 6.0 ms 6.0 ms
Onboard I/Os see table 1,2,3 see table 1,2,3 see table 1,2,3
max. digital inputs/outputs 8 / 6 8 / 6 8 / 6
max. analog inputs/outputs
2 / 1
Max.number of centralized inputs/outputs
Digital inputs 224+8 224+8 224+8
Digital outputs 168+6 168+6 168+6
Analog inputs 112 112 112+2
Analog outputs 112 112 112+1
Max. number of expansion I/O modules
centralized I/O modules 7 7 7
Decentralized I/O modules
on CS31 bus: up to 31
stations with up to 120 DI /
120 DO each
on CS31 bus: up to 31
stations with up to 120 DI /
120 DO each
on CS31 bus: up to 31
stations with up to 120 DI
/ 120 DO each
Data buffering in flash in flash in flash
Real-time clock (option with battery back-up) x x x
Program execution
cyclical x x x
time-controlled x x x
multi tasking x x x
interruption x x x
User program protection by password x x x
Internal interfaces
COM1:
RS485 x x x
Sub-D connection x x x
Progamming,Modbus,ASCII,CS31 x x x
COM2:(option)
RS485 x x x
Sub-D connection x x x
Progamming,Modbus,ASCII x x x
Integrated Ethernet
RUN/STOP switch x x x
LED display for power, status and error x x x

Related product manuals