Questions and Answers

  • V
    Victor JamesSep 10, 2025
    What does 'Phase reversal' mean on my ABB PSTX170 Controller?
    • E
      Eric SchmidtSep 10, 2025
      Phase reversal indicates that the phase sequence is incorrect, leading to current imbalance between the phases. To correct this, change the phase sequence on the line side to (L1-L2-L3). Then, restart the motor and check the main currents and voltage.
  • L
    Lisa JohnsonSep 8, 2025
    Why does my ABB PSTX170 Controller motor make a bad sound during both start and stop?
    • L
      Lisa LaraSep 8, 2025
      This could be due to several factors. First, try different settings for the Initial/End Voltage parameter. Also, experiment with different settings for the Current limit level or Torque limit level parameters. Ensure that you have the correct softstarter for the motor size. Make sure that the start and stop commands are not given at the same time. Check that the operation voltage is not below 175 V.
  • P
    Peter SmithSep 7, 2025
    What to do if loading parameters with Fieldbus does not work correctly on my ABB PSTX170?
    • S
      swalkerSep 7, 2025
      Ensure that the parameters match between the PLC and the Softstarter Fieldbus documentation for the used Fieldbus protocol. Make sure that the Auto mode bit of the binary output telegram setting is 1. Check if the HMI is set to remote control. Ensure that the Local Mode digital input on the ABB FieldBus Plug adapter is set to Remote. Make sure that Fieldbus disable control in DI is not connected. Verify that the Fieldbus control parameter is set to On.
  • H
    Heather WilsonAug 23, 2025
    What causes an electronic overload in my ABB PSTX170 Controller and how can I resolve it?
    • S
      Samantha MillerAug 23, 2025
      An electronic overload occurs when the motor current is too high for an extended period, often due to a high load on the motor shaft. To resolve this: * Examine start conditions and EOL settings. * Correct the reason for the overload. * Ensure the current limit level is not set too low. * Verify the ramp time for start is not too long. * Confirm the correct overload class is used. * Check that the Setting Ie parameter is correct.
  • J
    Joseph LambSep 4, 2025
    How do I fix an ABB Controller that shows a blank screen and no LED is active?
    • Y
      ybanksSep 4, 2025
      First, ensure that the supply voltage is properly connected, referring to the circuit diagram. Also check that the RJ45 plug is connected between the HMI and the softstarter, and that the RJ45 network cable is not damaged.
  • S
    Scott WellsSep 3, 2025
    Why is my ABB PSTX170 Controller showing a dark screen but the LED is active?
    • H
      Heather DoyleSep 3, 2025
      The controller is likely in power save mode. Simply touch a key on the keypad to exit this mode.
  • A
    Alexander BaileySep 2, 2025
    What to do if my ABB PSTX170 motor is humming or starts without a given start signal?
    • G
      Gary WilliamsSep 2, 2025
      This issue could be due to a few reasons. If it's a PSTX30...170 model, a bypass relay might be closed due to inaccurate handling. To resolve this, disconnect the operation voltage and the control supply voltage, remove the USB cable if connected, and then reconnect the voltage in the following sequence: first, the control supply voltage on terminals 1 and 2 (refer to chapter 5.1.2), wait 4 seconds, and then connect the operation voltage on terminals L1, L2, and L3. Alternatively, the bypass contactor/relay could be stuck in a closed position, or there might be a shorted thyristor. In either of these cases, it is best to speak to your ABB Sales Office.
  • A
    Adam CastilloSep 1, 2025
    How to troubleshoot phase loss in ABB PSTX170?
    • G
      Gloria SandovalSep 1, 2025
      Check that the mains are connected and that no line contactor or breaker is open. Inspect the fuses for all 3 phases, replacing any that are blown. Verify the operation network supply and correct it if there's a power loss on one or multiple phases. Ensure the contactor/breaker or external switch device is closed. If the line contactor opens too quickly at stop, control it with the Run signal relay on terminal 4, adding a time relay before the contactor opens. If Stop Ramp is not necessary, set Stop mode to direct stop.
  • E
    elliottpatrickAug 31, 2025
    What to do if my ABB Controller motor does not start when given a start command by the hardwire inputs?
    • J
      Jessica HurleyAug 31, 2025
      First, check the connections for start and stop. Make sure that the start and stop commands are not given at the same time. Ensure that the keypad is not in Local Control mode; if it is, push the R\L-key to change to Remote Control mode. Also, verify that the Fieldbus control parameter is set to No. Finally, reset any active or tripping events.
  • B
    Brittney HahnAug 29, 2025
    What does 'Thyristor overload' mean on my ABB PSTX170 Controller?
    • J
      Jared HobbsAug 29, 2025
      A thyristor overload indicates that the thyristors are too hot. Check the start conditions and the fans. If possible, decrease the current limit. Allow the temperature of the thyristors to decrease before restarting.

Summary

Getting Started and Safety

Manual Symbols and Safety Notes

Explains safety warnings and the meaning of symbols used in the manual.

Installation and Mounting

Mounting Safety Guidelines

Highlights safety advice and warnings related to the mounting process.

Electrical Connection

Connection Safety Precautions

Provides essential safety warnings for electrical connections.

HMI Operation

Softstarter Configuration

First Start-up Assistant

Guides the user through the initial power-up and basic setup.

Settings Navigation and Parameters

Troubleshooting Guide

Event List and Troubleshooting

Details common events, their causes, and recommended actions.

Short Circuit Current Ratings

ABB PSTX170 Specifications

General IconGeneral
TypeSoftstarter
Rated operational current Ie170 A
Protection classIP20
Rated operational voltage208-690 V AC
Operating temperature range-25°C to +60°C
Control supply voltage100 ... 240 V AC
Rated control supply voltage (Us)100 ... 240 V AC