3.2 Technical data
3.2.1 General
Table 3 General
General data Description
24 V output 24 V ± 5% Max 250 mA
Rated insulation voltage,
Ui
600 V / 690 V
Rated operation voltage,
Ue
208-600 / 690 V, 50 / 60 Hz
Rated supply voltage,Us 100-250 V, 50 / 60 Hz
Voltage tolerance +10% to -15%
Rated frequency 50 / 60 Hz
Frequency tolerances ± 10%
Rated impulse withstand
voltage
6 kV Operation circuit
4 kV Control and supply circuit
Relay outputs 3 programmable
Number of controlled
phases
3
Inputs Start, stop, 3 programmable inputs
(Digital I/O: In0, In1, In2), temperature
sensor input.
Outputs Relay outputs: K4 K5 K6.
Output relay
performance
250 V AC, Ith = 5A, Ie = 1.5A (AC-15)
Analog output 4-20 mA, 0-20 mA, 0-10 V, 0-10 mA
PTC input 2825 ohm ± 20% switch off resistance
1200 ohm ± 20% switch on resistance
Cooling system Fan
Recommended fuse
Control supply circuit
6 A Delayed
MCB use C characteristics
Communication 3 Fieldbus ports, Extension I/O
Communication
protocols
DeviceNet / Profibus DP / Modbus /
EtherNET/IP / Modbus TCP/ Profinet
3.2.2 Technical data for external keypad
Table 4 Technical data for external keypad
Display Display type
Status indicating LEDs Ready: Green
Run: Green
Protection: Yellow
Fault: Red
Ambient temperature Storage: -25 °C to +70 °C (-13 °F
to 158 °F)
Operation: -25 °C to +60 °C
(-13 °F to 140 °F)
Degree of protection IP66
UL approval Type 1
Type 4X
Type 12
Marine approvals Speak to your ABB sales office
3.2.3 Semi-conductor fuses
WARNING!
Semiconductor fuses must be used to keep the
warranty on the thyristors.
INFORMATION
To achieve a type 2 coordination, semiconductor
fuses must be used.
Table 5 Fuses ratings and power losses
Current
range
Max
power
loss at
rated I
e
Max fuse raiting - main
circuit
1) 2)
Bussmann fuses, DIN43 620
(Knife)
Power
require-
ments
supply
circuit
Holding
(VA) /
Type A W A Type Size
Pull-in
(VA)
PSTX30 9.0...30.0 0.8 100 170M1567 000 49/51
PSTX37 11.1...37.0 1.2 125 170M1568 000 49/51
PSTX45 13.5...45.0 1.8 160 170M1569 000 49/51
PSTX60 18.0...60.0 3.2 160 170M1569 000 49/51
PSTX72 21.6...72.0 4.7 250 170M1571 000 49/51
PSTX85 22.5...85.0 6.5 315 170M1572 000 49/51
PSTX105 31.8...106.0 10 400 170M3819 1* 49/51
PSTX142 42.9...143.0 18 500 170M5810 2 49/53
PSTX170 51.3...171.0 26 630 170M5812 2 49/53
PSTX210 63.0...210.0 48 630 170M5812 2 56/276
PSTX250 75.0...250.0 68 700 170M5813 2 56/276
PSTX300 90.0...300.0 97 800 170M6812 3 56/276
PSTX370 111.0...370.0 148 900 170M6813 3 56/276
PSTX470 141.0...470.0 99 900 170M6813 3 67/434
PSTX570 171.0...570.0 146 1000 170M6814 3 67/434
PSTX720 216.0...720.0 78 1250 170M8554 3 61/929
PSTX840 252.0...840.0 106 1500 170M6018 3 61/929
PSTX1050
3)
315.0...1050.0 165 1800 170M6020 3 68/929
PSTX1250
3) 4)
375.0...1250.0 234 2000 170M6021 3 68/929
1)
For the supply circuit 6 A delayed, for MCB use C characteristics.
2)
For inside delta connection the fuses shall be placed inside the delta. Contact ABB for
more information.
3)
170M6019 with fuse rating 1600 A should be used for 690 V version.
4)
For 690 V version, Bussmann fuses are only available for motors with rated current up
to 1150 A.
You can find more detailed information at:
http://applications.it.abb.com/SOC/
3.2.4 Weights
Table 6 Weights
Type Weight in kg Weight in lbs
PSTX30...105 6,1 13,5
PSTX142...170 9,6 21,2
PSTX210...370 12,7 27,9
PSTX470 25.5 55.1
PSTX570 27.5 59.5
PSTX720 ...840 46.2 101.4
PSTX1050 64.5 141.1
PSTX1250 65 143.3
3