Softstarters Type PSTX30...PSTX570 User Manual short form 1SFC132082M9901 15
EN
Table 6.7: Parameter list for operational function
For full parameter list, see I1SFC132081M0201
- Softstarters Type PSTX30...PSTX570, Installation and Commissioning Manual
available on: http://www.abb.com/lowvoltage
1
Operation functions
Parameter name Setting range Default value
1.1 Motor rated current Ie
PSTX30: 9 ... 30 A
1
30 A
2.1 Start mode Voltage ramp, Torque ramp,
Full voltage start
Voltage ramp
2.2 Stop mode Voltage ramp, Torque ramp,
No ramp
No ramp
2.3 Start ramp initial level 10 ... 99 % 30%
2.4 Start ramp time 1 ... 120s 10s
2.5 Stop ramp end level 10 ... 99% 30%
2.6 Stop ramp time 1 ... 120s 10s
3.1 Current limit type
Off, Normal, Dual, Ramp
Normal
3.2 Current limit level 1.5 ... 7.5 xIe 4.0 xIe
Kick start
1
On/Off
Off
Slow speed
1
Motor heating
1
Motor braking
1
Sequence start
1
Automatic restart
1
26.12 Faulty connection operation Stop-Manual,
Stop-Automatic
Stop-Manual
28.5 Step down level 10 ... 100% 80%
28.41 System mode Normal, Demo, Small motor Normal
28.43 Mains connection Auto, In line, Inside delta UI,
Inside delta IU,
Two phase (L1 Shorted),
Two phase (L2 Shorted),
Two phase (L3 Shorted)
Auto
28.42 Limp mode On/Off Off
This is a selection of the most commonly used parameters.
For complete parameter list and setting range, see:
1SFC132081M0201 - Softstarters type PSTX30...PSTX570, Installation and Commissioning Manual
available on: http://www.abb.com/lowvoltage