21.14 Current imbalance trip time 0.1 ... 100.0 1 5.0 s
22 Warnings list 3
22.01 Over voltage level 208 ... 850 V 0 104 650 V
22.02 Over voltage trip time 0.1 ... 100.0 s 1 105 1.0 s
22.03 Over voltage out
Eventgroup 0 ... 6
0 107 0000100
22.04 Over voltage On / Off 0 106 Off
22.05 Under voltage level 208 ... 850 V 0 108 208 V
22.06 Under voltage trip time 0.1 ... 100.0 s 1 109 0.5 s
22.07 Under voltage out
Eventgroup 0 ... 6
0 111 0000100
22.08 Under voltage On / Off 0 110 Off
22.09 Voltage imb level 1 ... 100 0 119 5
22.10 Voltage imb out Eventgroup 0 ... 6 0 120 0000100
22.11 Voltage imbalance On / Off 0 118 Off
22.12 Voltage imbalance trip time 0.1 ... 100.0 s 1 5.0 s
23 Warnings list 4
23.01 EOL time-to-trip time 1 ... 1000 s 0 114 5 s
23.02 EOL time-to-trip out Eventgroup 0 ... 6 0 112 0000100
23.03 EOL time-to-trip On / Off 0 113 Off
23.04 THD(U) level 1 ... 100% 0 116 10%
23.05 THD(U) out Eventgroup 0 ... 6 0 117 0000100
23.06 THD(U) On / Off 0 115 Off
23.07 Short circuit out Eventgroup 0 ... 6 0 129 0000100
23.08 Short circuit On / Off 0 121 Off
23.09 THD(U) trip time 0.1 ... 100.0 s 1 10.0 s
24 Warnings list 5
24.01 Number of starts limit 1 ... 65535 0 - 65535
24.02 Number of starts out Eventgroup 0 ... 6 0 - 0000100
24.03 Number of starts
On / Off
0-Off
24.04 Faulty fan out Eventgroup 0 ... 6 0 80 0000100
24.05 Faulty fan On / Off 0 79 On
24.06 Modbus_RTU w/o auxport out Eventgroup 0 ... 6 0 176 0000100
24.7 Phase loss trip time 0.5 ... 100.0 1 3.0
24.8 Phase loss out Eventgroup 0 ... 6 0 0000100
24.9 Phase loss On / Off 0 Off
24.10 Motor run time limit 0 ... 100000 0 10000
24.11 Motor run time out Eventgroup 0 ... 6 0 0000100
24.12 Motor run time On / Off 0 Off
25 Internal faults
25.01 Shunt fault out Eventgroup 0 ... 6 0 42 0000001
25.02 Shunt fault op Stop-Manual, Stop-Automatic 0 272 Stop-Manual
25.03 Short circuit out Eventgroup 0 ... 6 0 50 0000001
25.04 Short circuit fault op Stop-Manual, Stop-Automatic 0 273 Stop-Automatic
25.05 Open circuit thyr out Eventgroup 0 ... 6 0 44 0000001
25.06 Open circuit thyr op Stop-Manual, Stop-Automatic 0 274 Stop-Manual
25.07 Thyristor OL out Eventgroup 0 ... 6 0 47 0000001
25.08 Thyristor OL op Stop-Manual, Stop-Automatic 0 275 Stop-Manual
25.09 Heatsink over temp out Eventgroup 0 ... 6 0 48 0000001
25.10 Heatsink over temp op Stop-Manual, Stop-Automatic 0 276 Stop-Manual
25.11 Unspecified fault out Eventgroup 0 ... 6 0 43 0000001
25.12 Unspecified fault op Stop-Manual, Stop-Automatic 0 277 Stop-Manual
26 External faults
26.01 Phase loss out Eventgroup 0 ... 6 0 96 0000001
26.02 Phase loss op Stop-Manual, Stop-Automatic 0 278 Stop-Manual
26.03 Bad network out Eventgroup 0 ... 6 0 36 0000001
26.04 Bad network op Stop-Manual, Stop-Automatic 0 279 Stop-Manual
26.05 Low supply voltage out Eventgroup 0 ... 6 0 46 0000001
26.06 Low supply voltage op Stop-Manual, Stop-Automatic 0
280
Stop-Manual
26.07 High current out Eventgroup 0 ... 6 0 49 0000001
26.08 High current op Stop-Manual, Stop-Automatic 0 281 Stop-Manual
7