Loading...
1SFC132104M0201 | Application manual: Waste water pump | Connection 13
3.2.5 Connecting line contactor and
Run pilot light
The output relay gives a signal depending on the selected
function. K4 is set to Run by default.
Connect the cables for controlling the line contactor to
terminal 4 and 5 for NO control of the contactor.
See Figure 12.
Connect the green Run pilot light parallel to the supply
voltage for the line contactor, e.g. by using an auxiliary
contact block to the line contactor.
Tightening torques and cable dimensions.
3.2.6 Connecting Event pilot light
The output relay gives a signal depending on the selected
function. K6 is set to Event by default.
Connect the cables for the yellow Fault and Protection
pilot light to terminal 10 and 11 for NO control of the pilot
light. See Figure 13.
Tightening torques and cable dimensions.
3.2.7 Extension I/O for extra inputs and
outputs (optional)
If more inputs and outputs are needed, connect
accessory DX111-FBP.0 (1SAJ611000R0101) from ABB.
This will give additional:
8 digital input
4 ouput relay
1 analog output
The cables shall be connected to terminals 23, 24, 28
and 30. See Figure 14.
Tightening torques and cable dimensions.
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
AWG 12 ... 24
0,5 Nm
4,3 lb.in
3,5 x 0,6 mm
(0.138 x 0.024 in)
M3
23 24 25 26 27
T1 T2 T3
28 29 30
+(B) -(A) +24V +GND
Analog outTemp InCom 3
12
1SFC132081M0201
Figure 12: Programmable output relay K4, terminals4,5and6
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
AWG 12 ... 24
0,5 Nm
4,3 lb.in
3,5 x 0,6 mm
(0.138 x 0.024 in)
M3,5
L
100-250V
50/60 Hz K4 K5 K6
Start Stop In0 In1 In2 GND +24V
N
1SFC132081M0201
13
1SFC132081M0201
Figure 13: Programmable output relay K6, terminals10,11and12
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
AWG 12 ... 24
0,5 Nm
4,3 lb.in
3,5 x 0,6 mm
(0.138 x 0.024 in)
M3
L
100-250V
50/60 Hz K4 K5 K6
Start Stop In0 In1 In2 GND +24V
N
1SFC132081M0201
14
A
23 24 25 26 27
T1 T2 T3
28 29 30
+(B) -(A) +24V +GND
Analog outTemp InCom 3
1SFC132081M0201
Figure 14: Extension I/O
2