116 Functions | Installation and commissioning manual | 1SFC132081M0201
7.18.12 Short circuit warning
There is an internal short circuit and limp mode is
enabled. If limp mode is off, this is a short circuit fault
instead.
Speak to ABB Sales Offices for service.
Short circuit warning has these parameters:
Parameter Description Setting range Default value
23.07 Short circuit out Identifies the Event groups this warning is
part of.
Eventgroup 0 ... 6 0000100
23.08 Short circuit Enables Short circuit warning. Off, On On
7.18.13 Number of starts warning
Number of starts warning
Number of starts warning has these parameters:
Parameter Description Setting range Default value
24.01 Number of starts limit Max number of starts 1 ... 65535 65535
24.02 Number of starts out Specifies the Event groups this warning
belongs to.
Eventgroup 0 ... 6 0000100
24.03 Number of starts Enables Number of starts warning Off, On Off
7.18.14 Modbus configuration warning
The built-in modbus RTU slave is enabled (parameter
12.02) but the Com3 function is not set to modbus RTU
slave. To use modbus RTU, enable the RTU slave and set
the modbus RTU slave to use the Com3 port.
Modbus configuration warning has these parameters:
Parameter Description Setting range Default value
24.06 Modbus_RTU w/o auxport out Identifies the Event groups this
warning belong to.
Eventgroup 0 ... 6 0000100
7.18.15 Phase loss warning
Phase loss warning.
Phase loss warning has these parameters:
Parameter Description Setting range Default value
24.07 Phase loss trip time Trip time in seconds 0.5 ... 100.0 s 3.0 s
24.08 Phase loss out Specifies the Event groups this
warning belongs to.
Eventgroup 0 ... 6 0000100
24.09 Phase loss Enables Phase loss warning Off, On Off