- 16 -
000430BG
2 - Characteristics
Characteristics and technical data
Table: Technical Data
PVI-6.0-TL-OUTD PVI-8.0-TL-OUTD PVI-10.0-TL-OUTD PVI-12.5-TL-OUTD
Input
Absolute Maximum
Input Voltage (Vmax,abs)
900 V
Rated Input Voltage (Vdcr) 580 V
Input start-up voltage (Vstart) 360 V (adj. 250...500 V)
Input operating interval
(Vdcmin...Vdcmax)
0.7 x Vstart...
850
V
Input Nominal Power(Pdcr) 6200 W 8250 W 10300 W 12800 W
Number of Independent MPPT 2
Maximum input power for Each
MPPT (PMPPTmax)
4200 W 5500 W 6500 W 8000 W
Input voltage interval
(VMPPTmin ... VMPPTmax) to Pacr
(parallel MPPT conguration)
200…750 V 270…750 V 300…750 V 360...750 V
DC Power limiting for each
MPPT with Independent MPPT
Conguration to Pacr, maximum
unbalance example
4200 W
[250V≤VMPPT≤750V]
other channel:
Pdcr-4200W
[175V≤VMPPT≤750V]
5500 W
[320V≤VMPPT≤750V]
other channel:
Pdcr-5500W
[175V≤VMPPT≤750V]
6500 W
[380V≤VMPPT≤750V]
other channel:
Pdcr-6500W
[225V≤VMPPT≤750V]
8000 W
[445V≤VMPPT≤750V]
other channel:
Pdcr-8000W
[270V≤VMPPT≤750V]
Maximum DC Input Current
(Idcmax) / for each MPPT
(IMPPTmax)
34.0 A / 17.0 A 34.0 A / 17.0 A 34.0 A / 17.0 A 36.0 A / 18.0 A
Maximum Return current
(AC side vs DC side)
Negligible
Number of DC Connection Pairs
in Input for each MPPT
2 pair for -S version; 3 pair for standard and -FS version
2 pair for -S version; 3 pair for standard and -FS version
DC Input Connector type
(components indicated or equi-
valents)
Connector PV Tool Free WM / MC4
Type of photovoltaic panels that
can be connected at input accor-
ding to IEC 61730
Class A
Input protection
Reverse Polarity Protection
Inverter protection only, from limited current source, for standard and -S versions,
and for -FS version when max 2 strings are connected
Input Overvoltage protection for
each MPPT - Varistors
2
Maximum short-circuit current for
each MPPT
22.0 A
Insulation Check Complying with the local standard
DC Disconnect Switch rating
(-S Version)
Max. 25.0 A / 1000 V
Fuse rating (-FS Version) Max. 12.0 A / 1000 V