Arc Protection Relay REA 10_
1MRS750929-MBG
11
Conducted RF emission (mains terminal) EN 55011, class A, IEC 60255-25
Radiated RF emission EN 55011, class A,
IEC 60255-25
SWC tests according to ANSI/IEEE C37.90.1-2002:
Oscillatory tests 2.5 kV
Fast transient test 4 kV
Power frequency (50 Hz) magnetic field according to IEC61000-4-8 300 A/m, continuous
Voltage dips and short interruptions according to
IEC 61000-4-11:
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
Table 17: CE approval
Complies with the EMC directive 89/336/EEC and the LV directive
73/23/EEC
EN 50263
EN 60255-6
Table 18: Mechanical tests
Vibration tests (sinusoidal) according to IEC 60255-21-1 class 1
Shock and bump test according to IEC 60255-21-2 class 1
Seismic tests according to IEC 60255-21-3 class 2
Table 16: Electromagnetic compatibility tests (continued)