is the steady state heat content
I
is the largest phase load current
I
ref
is the given reference load current
2
operate Bx ref Trip
III
is the operate level heat content
I
Bx
is the selected base current based cooling
system
ON
/
OFF
I
Trip
is the operate level load current
θ
n
is the current heat content
Consider that the given system has IBase of 1000 A and the cooling system is ON.
The following settings are used to calculate the operate time:
IRef
110%
IBase1
110% of IB
IBase2
120% of IB
Tau1
150 min
Tau2
90 min
IHighTau1
110% of IB1
Tau1High
125% of tC1
ILowTau1
90% of IB1
Tau1Low
75% of tC1
IHighTau2
110% of IB2
Tau2High
115% of tC2
ILowTau2
90% of IB2
Tau2Low
85% of tC2
ITrip
120% of IBx
ThetaInit
50%
ResLo
60% of Itr
As the cooling system is ON, IBase2 is selected as the base current and Tau2
setting is selected as the time constant.
For example, the largest phase load current is taken as 1800 A, then:
2
1800
1.
2677685.95
1
final
2
(1.2 1000 1.1 1.2) 2509056
operate
Section 7 1MRK 505 388-UEN B
Current protection
122 Busbar protection REB650 2.2 IEC
Application manual