Table 33. Four step negative sequence overcurrent protection NS4PTOC
Function Range or value Accuracy
Operate current, step 1 - 4 (1-2500)% of
lBase
±1.0% of I
r
at I £ I
r
±1.0% of I at I > I
r
Reset ratio > 95% at (10-2500)% of
IBase
-
Independent time delay at 0 to
2 x I
set
, step 1 - 4
(0.000-60.000) s ±0.2% or ±35 ms whichever is
greater
Minimum operate time for
inverse curves, step 1 - 4
(0.000 - 60.000) s ±0.2% or ±35 ms whichever is
greater
Inverse time characteristics,
see table 143, table 144 and
table 145
16 curve types See table 143, table 144 and
table 145
Minimum operate current, step
1 - 4
(1.00 - 10000.00)% of
IBase
±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Relay characteristic angle
(RCA)
(-180 to 180) degrees
±2.0 degrees
Operate current for directional
release
(1–100)% of
IBase
For RCA ±60 degrees:
±2.5% of I
r
at I ≤ I
r
±2.5% of I at I > I
r
Minimum polarizing voltage (1–100)% of
UBase
±0.5% of U
r
Minimum polarizing current (2-100)% of
IBase
±1.0% of I
r
Real part of negative sequence
source impedance used for
current polarization
(0.50-1000.00) W/phase
-
Imaginary part of negative
sequence source impedance
used for current polarization
(0.50–3000.00) W/phase
-
Operate time, start non-
directional at 0 to 2 x I
set
Min. = 15 ms
Max. = 30 ms
-
Reset time, start non-
directional at 2 to 0 x I
set
Min. = 15 ms
Max. = 30 ms
-
Operate time, start non-
directional at 0 to 10 x I
set
Min. = 5 ms
Max. = 20 ms
-
Reset time, start non-
directional at 10 to 0 x I
set
Min. = 20 ms
Max. = 35 ms
-
Critical impulse time 10 ms typically at 0 to 2 x I
set
-
Impulse margin time 15 ms typically -
Transient overreach <10% at τ = 100 ms -
1MRK 511 361-BEN B
Bay control REC670 2.1 IEC
Product version: 2.1