Section 13 Reset
About this chapter
This chapter describes how to reset the IED and when this is necessary.
13.1
Reset guide
13.1.1 Reset counters
13.1.1.1 Reset autorecloser SMBRREC
The recorded number of reclosings are reset under Reset counters in the HMI tree.
Main menu/Reset/Reset counters/Autorecloser(RREC,79)/AR
In the dialog box that appears, choose YES to reset.
13.1.1.2 Circuit breaker SXCBR
The circuit breaker counter is reset under Reset counter in the HMI tree.
Main menu/Reset/Reset counters/CircuitBreaker(XCBR)/XC
In the dialog box that appears, choose YES to reset.
13.1.1.3 Circuit switch SXSWI
The circuit switch counter is reset under Reset counters in the HMI tree.
Main menu/Reset/Reset counters/CircuitSwitch(XSWI)/XS
In the dialog box that appears, choose YES to reset.
13.1.1.4 Reset event counter CNTGGIO
The event counter is reset under Reset counters in the HMI tree.
Main menu/Reset/Reset counters/EventCounter(GGIO)/CNT
13.1.1.5 Reset pulse counter PCGGIO
The Pulse counter is reset under Reset counters menu in the HMI tree.
1MRK 511 188-UEN C Section 13
Reset
93
Operator's manual