EasyManua.ls Logo

ABB REF 542plus - Examples of Communication System Addressing

ABB REF 542plus
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Subnet 1
0100 1000=48h =72
Subnet 2 0100 1001=49h =73
Subnet mask 1111 1110=FEh =254
Subnet mask 1111 1100=FDh =252 (Next possible
alternative)
The next possible alternative mask address allows also a wider range of IP
addresses to have access to subnet 1 and 2. It means that also other computers
can have access to them.
In the example, it would allow the 3rd IP address identifier 48h;49h;4ah;4bh
which is in decimal 72;73;74;75.
6.4.7. Examples of communication system addressing
Communication system addressing should be based on the following network
design rules:
*
The router and REF 542plus devices belonging to the LAN plant have to
have the same subnet mask address.
*
The default gateway address configured in each REF 542plus has to be
equal to the IP address of the router.
*
The IP addresses of REF 542plus have to be consecutive.
42
REF 542plus
Multifunctional Protection and Switchbay
Control Unit
Installation Manual for Web Interface
Installation manual
1MRS755865

Table of Contents

Other manuals for ABB REF 542plus

Related product manuals