To change a parameter:
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select the main menu group CONFIGURATION and the
wanted group menu, and press
.
3. Use
or to select the wanted parameter (for example UNIT ADDRESS :
xxx) or a set of parameters (for example SPA SETTINGS). In case of a set of
parameters, use arrow buttons until you reach the wanted parameter.
4. Press
to enter the setting mode and give the password if required.
5. The parameter text (enumerator) or the first digit of the parameter setting value
starts to flash. Set the enumerator or the digit/character by using
and .
Activate the next digit/character to be set by pressing
or . When setting an
enumerator, however, the left and right arrows have no function.
6. To store a new value and return the display to the view mode, press
. If the
parameter is of numerical kind, the display confirms the storage by flashing "--
-" once on the display.
7. To exit the setting mode without storing the changes, press
once before
confirming and the display returns to the view mode.
8. Press
once more to return the display to the idle mode.
If a setting value outside the allowed limits is confirmed in the setting
mode, the former value is restored.