PT 100 PT 250 NI 100 NI 120 CU 10
R °C °C °C °C °C
120 51.6 - 35 0 -
150 130.5 - 82.6 43.3 -
160 157.2 - 97.5 56.8 -
180 - - 125.5 84 -
200 - -50.8 151.8 107 -
220 - -30.6 176.3 130 -
240 - -10.2 199.3 151.8 -
270 - 20.5 - 182.2 -
300 - 51.6 - -
330 - 82.9 - -
360 - 114.6 - -
390 - 146.5 - -
430 - 189.6 - -
RTD connector numbering is an example of a 4U case. See the
technical manual for complete terminal diagrams.
GUID-327C519C-BA13-4161-A62C-B94074ECEC01 V1 EN
Figure 4: Testing sensor/resistance input by connecting resistor directly to
connector
Voltage type measurement mode can be verified by connecting a voltage source
on the input and measure input voltage at the same time by multimeter, for
example, 5 VDC voltage.
Section 5 1MRS756801 E
Troubleshooting
38 630 series
Commissioning Manual