96
Instantaneous overcurrent protection
(IOC)
&KDSWHU
9HULI\LQJVHWWLQJVE\VHFRQGDU\
LQMHFWLRQ
 ,QVWDQWDQHRXVRYHUFXUUHQWSURWHFWLRQ,2&
Prepare the terminal for verification of settings as outlined in section “Preparing for
test” in this chapter.
To verify the settings the following fault type should be tested:
One for a phase-to-earth fault
Ensure that the maximum continuous current of the terminal does not exceed four times
its rated value.
 0HDVXULQJWKHRSHUDWHOLPLWRIVHWYDOXHV
 3KDVHRYHUFXUUHQWSURWHFWLRQ
3URFHGXUH
 ,QMHFWDSKDVHFXUUHQWLQWKHWHUPLQDOZLWKVWDUWEHORZWKHVHW
WLQJYDOXH
 ,QFUHDVHWKHLQMHFWHGFXUUHQWLQWKH/QSKDVHXQWLOWKH
,2&75/QQ VLJQDODSSHDUV
 6ZLWFKRIIWKHIDXOWFXUUHQW
Observe the maximum permitted overloading of the current cir-
cuits in the terminal.
 &RPSDUHWKHPHDVXUHGRSHUDWLQJFXUUHQWZLWKWKHVHWYDOXH
 5HVLGXDORYHUFXUUHQWSURWHFWLRQQRQGLU
3URFHGXUH
 ,QMHFWDSKDVHFXUUHQWLQWKHWHUPLQDOZLWKVWDUWEHORZWKHVHW
WLQJYDOXH
 ,QFUHDVHWKHLQMHFWHGFXUUHQWLQWKH/QSKDVHXQWLOWKH
,2&751VLJQDODSSHDUV
 6ZLWFKRIIWKHIDXOWFXUUHQW
Observe the maximum permitted overloading of the current cir-
cuits in the terminal.
 &RPSDUHWKHPHDVXUHGRSHUDWLQJFXUUHQWZLWKWKHVHWYDOXH