44
Checking the self supervision signals &KDSWHU
(QHUJLVLQJWKHWHUPLQDO
&KHFNLQJWKHVHOIVXSHUYLVLRQIXQFWLRQ
1DYLJDWLQJWKHPHQXV
This procedure describes how to navigate the menus in order to find the reason of an
internal failure when indicated by the flashing green LED of the HMI module.
3URFHGXUH
'LVSOD\WKHVHOIVXSHUYLVLRQPHQX
Navigate the menus to:
7HUPLQDO5HSRUW
6HOI6XSHUY
6FUROOWKHVXSHUYLVLRQYDOXHVWRLGHQWLI\WKHUHDVRQRIWKHIDLO
XUH
Use the /HIW and/or 5LJKW arrow buttons to scroll between values.
6HOIVXSHUYLVLRQ+0,GDWD
7DEOH 2XWSXWVLJQDOVIRUWKHVHOIVXSHUYLVLRQIXQFWLRQ
,QGLFDWHGUHVXOW 3RVVLEOHUHDVRQ 3URSRVHGDFWLRQ
InternFail = OK No problem detected. None.
InternFail = Fail A failure has occurred. Check the rest of the indicated results to
find the fault.
InternWarning = OK No problem detected. None.
InternWarning =
Warning
A warning has been
issued.
Check the rest of the indicated results to
find the fault.
MPM-modFail = OK No problem detected. None.
MPM-modFail = Fail The main processing
module has failed.
Contact your ABB representative for ser-
vice.
MPM-modWarning =
OK
No problem detected. None.
MPM-modWarning =
Warning
There is a problem
with:
• the real time clock.
• the time synchroni-
zation.
Set the clock.
If the problem persists, contact your ABB
representative for service.