83
Breaker failure protection (BFP) &KDSWHU
9HULI\LQJVHWWLQJVE\VHFRQGDU\
LQMHFWLRQ
 $SSO\WKHIDXOWFRQGLWLRQZLWKFXUUHQWRYHUWKHVHWYDOXH
 9HULI\WKDWUHWULSLVDFKLHYHGDIWHUWWKDWEDFNXSWULSLV
DFKLHYHGDIWHUW
 &KHFNLQJWKHUHWULSIXQFWLRQZLWKRXWFXUUHQWFKHFN
3URFHGXUH
 6HW5HWULS7\SH 1R,!FKHFN
 $SSO\WKHIDXOWFRQGLWLRQZLWKFXUUHQWEHORZWKHVHWYDOXH
 9HULI\WKDWUHWULSLVDFKLHYHGDIWHUW
 $SSO\WKHIDXOWFRQGLWLRQZLWKFXUUHQWRYHUWKHVHWYDOXH
 9HULI\WKDWEDFNXSWULSLVDFKLHYHGDIWHUW
 &RPSOHWLQJWKHWHVW
Continue to test another function or complete the test by setting the test mode to off.
Restore connections and settings to the original values, if they were changed for testing
purpose.