IEC 61850 name AFL-Common SA name Description DPI value FUN INF In Use ASDU GI Coding
SRGAPC1, flip-flop reset control (all variants)
LD0.SRGAPC1.Rs1.ctlVal - Reset SRGAPC1 flip-flop 1 10=Reset 11 101 1 20 0 1
LD0.SRGAPC1.Rs2.ctlVal - Reset SRGAPC1 flip-flop 2 10=Reset 11 102 1 20 0 1
LD0.SRGAPC1.Rs3.ctlVal - Reset SRGAPC1 flip-flop 3 10=Reset 11 103 1 20 0 1
LD0.SRGAPC1.Rs4.ctlVal - Reset SRGAPC1 flip-flop 4 10=Reset 11 104 1 20 0 1
LD0.SRGAPC1.Rs5.ctlVal - Reset SRGAPC1 flip-flop 5 10=Reset 11 105 1 20 0 1
LD0.SRGAPC1.Rs6.ctlVal - Reset SRGAPC1 flip-flop 6 10=Reset 11 106 1 20 0 1
LD0.SRGAPC1.Rs7.ctlVal - Reset SRGAPC1 flip-flop 7 10=Reset 11 107 1 20 0 1
LD0.SRGAPC1.Rs8.ctlVal - Reset SRGAPC1 flip-flop 8 10=Reset 11 108 1 20 0 1
Negative sequence overcurrent protection (2 stages), all variants
LD0.NSPTOC1.Str.general NSPTOC1.START Stage1 start 10=Stage1 start 21 84 1 2 1 1
LD0.NSPTOC1.Op.general NSPTOC1.OPERATE Stage1 operate 10=Stage1 operate 21 90 1 2 0 1
LD0.NSPTOC2.Op.general NSPTOC2.OPERATE Stage2 operate 10=Stage2 operate 21 91 1 2 0 1
LD0.NSPTOC2.Str.general NSPTOC2.START Stage2 start 10=Stage2 start 21 94 1 2 1 1
Fuse failure protection (1 stage), FE05,06,07
LD0.SEQRFUF1.Str.general SEQRFUF1.FUSEF_U General start 10=General Start 22 84 1 2 1 1
LD0.SEQRFUF1.Str3Ph.general SEQRFUF1.FUSEF_3PH 3 phase start 10=3 phase start 22 94 1 2 1 1
Current circuit failure protection (1 stage), FE05,06,07
CTRL.CCRDIF1.Alm.stVal CCRDIF1.FAIL Alarm 10 = Alarm 23 1 1 1 1 1
CTRL.CCRDIF1.Op.general CCRDIF1.ALARM Operate 10 = Operate 23 90 1 2 0 1
Admittance based earhtfault protection, 3 stages (FE01,02,05,06,07)
LD0.EFPADM1.Str.general EFPADM1.START Stage1 start 10 = Stage 1 start 25 84 1 2 1 1
LD0.EFPADM1.Op.general EFPADM1.OPERATE Stage1 operate 10 = Stage 1 operate 25 90 1 2 0 1
LD0.EFPADM2.Op.general EFPADM2.OPERATE Stage2 operate 10 = Stage 2 operate 25 91 1 2 0 1
LD0.EFPADM2.Str.general EFPADM2.START Stage2 start 10 = Stage 2 start 25 94 1 2 1 1
LD0.EFPADM3.Str.general EFPADM3.START Stage3 start 10 = Stage 3 start 25 96 1 2 1 1
LD0.EFPADM3.Op.general EFPADM3.OPERATE Stage3 operate 10 = Stage 3 operate 25 98 1 2 0 1
Synchrocheck indications (FE08)
LD0.SECRSYN1.SynPrg.stVal SECRSYN1.SYNC_INPRO Synchonization in progress 10 = In progress 26 1 1 1 1 1
LD0.SECRSYN1.FailCmd.stVal SECRSYN1.CMD_FAIL_AL CB closing request failed 10 = Request failed 26 2 1 1 0 1
LD0.SECRSYN1.FailSyn.stVal SECRSYN1.CL_FAIL_AL CB closing command failed 10 = Command failed 26 3 1 1 0 1
Frequency protection (FRPFRQ1..3), 3 stages (FE08)
LD0.FRPTRC1.Str.general FRPFRQ1.START Stage 1 start 1 = Stage1 start 27 11 1 2 1 1
LD0.FRPTOF1.Op.general FRPFRQ1.OPR_OFRQ Operate 1 signal for overfrequency 1 = Stage1 overfrequency operate 27 12 1 2 0 1
LD0.FRPTUF1.Op.general FRPFRQ1.OPR_UFRQ
Operate 1 signal for
underfrequency 1 = Stage1 underfrequency operate 27 13 1 2 0 1
LD0.FRPFRC1.Op.general FRPFRQ1.OPR_FRG
Operate 1 signal for frequency
gradient 1 = Stage1 frequency gradient operate 27 14 1 2 0 1
LD0.FRPTRC2.Str.general FRPFRQ2.START Stage 2 start 1 = Stage2 start 27 21 1 2 1 1
LD0.FRPTOF2.Op.general FRPFRQ2.OPR_OFRQ Operate 2 signal for overfrequency 1 = Stage2 overfrequency operate 27 22 1 2 0 1
Table continues on next page
1MRS756712 C Section 2
IEC 60870-5-103 data mappings
REF615 15
Point List Manual