IEC 61850 name AFL-Common SA name Description DPI value FUN INF In Use ASDU GI Coding
LD0.FRPTUF2.Op.general FRPFRQ2.OPR_UFRQ
Operate 2 signal for
underfrequency 1 = Stage2 underfrequency operate 27 23 1 2 0 1
LD0.FRPFRC2.Op.general FRPFRQ2.OPR_FRG
Operate 2 signal for frequency
gradient 1 = Stage2 frequency gradient operate 27 24 1 2 0 1
LD0.FRPTRC3.Str.general FRPFRQ3.START Stage 3 start 1 = Stage3 start 27 31 1 2 1 1
LD0.FRPTOF3.Op.general FRPFRQ2.OPR_OFRQ Operate 3 signal for overfrequency 1 = Stage3 overfrequency operate 27 32 1 2 0 1
LD0.FRPTUF3.Op.general FRPFRQ3.OPR_UFRQ
Operate 3 signal for
underfrequency 1 = Stage3 underfrequency operate 27 33 1 2 0 1
LD0.FRPFRC3.Op.general FRPFRQ3.OPR_FRG
Operate 3 signal for frequency
gradient 1 = Stage3 frequency gradient operate 27 34 1 2 0 1
Three-phase directional overcurrent protection (3 stages), FE06,07
LD0.DPHHPTOC1.Str.phsA - High stage Start[.phsA] 10=High stage phsA start 32 44 0 2 1 1
LD0.DPHHPTOC1.Str.phsB - High stage Start[.phsB] 10=High stage phsB start 32 45 0 2 1 1
LD0.DPHHPTOC1.Str.phsC - High stage Start[.phsC] 10=High stage phsC start 32 46 0 2 1 1
LD0.DPHLPTOC2.Str.phsA - Low(2) stage Start[.phsA] 10=Low(2) stage phsA start 32 54 0 2 1 1
LD0.DPHLPTOC2.Str.phsB - Low(2) stage Start[.phsB] 10=Low(2) stage phsB start 32 55 0 2 1 1
LD0.DPHLPTOC2.Str.phsC - Low(2) stage Start[.phsC] 10=Low(2) stage phsC start 32 56 0 2 1 1
LD0.DPHLPTOC1.Str.phsA - Low(1) stage Start[.phsA] 10=Low(1) stage phsA start 32 64 0 2 1 1
LD0.DPHLPTOC1.Str.phsB - Low(1) stage Start[.phsB] 10=Low(1) stage phsB start 32 65 0 2 1 1
LD0.DPHLPTOC1.Str.phsC - Low(1) stage Start[.phsC] 10=Low(1) stage phsC start 32 66 0 2 1 1
LD0.DPHLPTOC1.Str.general DPHLPDOC1.START Low(1) stage Start[.general] 10=Low(1) stage start 32 84 1 2 1 1
LD0.DPHLPTOC1.Op.general DPHLPDOC1.OPERATE Low(1) stage Operate[.general] 10=Low(1) stage operate 32 90 1 2 0 1
LD0.DPHLPTOC2.Op.general DPHLPDOC2.OPERATE Low(2) stage Operate[.general] 10=Low(2) stage operate 32 91 1 2 0 1
LD0.DPHLPTOC2.Str.general DPHLPDOC2.START Low(2) stage Start[.general] 10=Low(2) stage start 32 94 1 2 1 1
LD0.DPHHPTOC1.Str.general DPHHPDOC1.START High stage Start[.general] 10=High stage start 32 96 1 2 1 1
LD0.DPHHPTOC1.Op.general DPHHPDOC1.OPERATE High stage Operate[.general] 10=High stage operate 32 98 1 2 0 1
Phase overvoltage protection (3 stages), FE06,07
LD0.PHPTOV3.Str.phsA - Stage 3 Start[.phsA] 10=Stage 3 phsA start 40 44 0 2 1 1
LD0.PHPTOV3.Str.phsB - Stage 3 Start[.phsB] 10=Stage 3 phsB start 40 45 0 2 1 1
LD0.PHPTOV3.Str.phsC - Stage 3 Start[.phsC] 10=Stage 3 phsC start 40 46 0 2 1 1
LD0.PHPTOV2.Str.phsA - Stage 2 Start[.phsA] 10=Stage 2 phsA start 40 54 0 2 1 1
LD0.PHPTOV2.Str.phsB - Stage 2 Start[.phsB] 10=Stage 2 phsB start 40 55 0 2 1 1
LD0.PHPTOV2.Str.phsC - Stage 2 Start[.phsC] 10=Stage 2 phsC start 40 56 0 2 1 1
LD0.PHPTOV1.Str.phsA - Stage 1 Start[.phsA] 10=Stage 1 phsA start 40 64 0 2 1 1
LD0.PHPTOV1.Str.phsB - Stage 1 Start[.phsB] 10=Stage 1 phsB start 40 65 0 2 1 1
LD0.PHPTOV1.Str.phsC - Stage 1 Start[.phsC] 10=Stage 1 phsC start 40 66 0 2 1 1
LD0.PHPTOV1.Str.general PHPTOV1.START Stage 1 Start[.general] 10=Stage 1 start 40 84 1 2 1 1
LD0.PHPTOV1.Op.general PHPTOV1.OPERATE Stage 1 Operate[.general] 10=Stage 1 operate 40 90 1 2 0 1
LD0.PHPTOV2.Op.general PHPTOV2.OPERATE Stage 2 Operate[.general] 10=Stage 2 operate 40 91 1 2 0 1
LD0.PHPTOV2.Str.general PHPTOV2.START Stage 2 Start[.general] 10=Stage 2 start 40 94 1 2 1 1
LD0.PHPTOV3.Str.general PHPTOV3.START Stage 3 Start[.general] 10=Stage 3 start 40 96 1 2 1 1
Table continues on next page
Section 2 1MRS756712 C
IEC 60870-5-103 data mappings
16 REF615
Point List Manual