IEC 61850 name AFL-Common SA name Description DPI value FUN INF In Use ASDU GI Coding
LD0.PHPTOV3.Op.general PHPTOV3.OPERATE Stage 3 Operate[.general] 10=Stage 3 operate 40 98 1 2 0 1
Phase undervoltage protection (3 stages), FE06,07
LD0.PHPTUV3.Str.phsA - Stage 3 Start[.phsA] 10=Stage 3 phsA start 41 44 0 2 1 1
LD0.PHPTUV3.Str.phsB - Stage 3 Start[.phsB] 10=Stage 3 phsB start 41 45 0 2 1 1
LD0.PHPTUV3.Str.phsC - Stage 3 Start[.phsC] 10=Stage 3 phsC start 41 46 0 2 1 1
LD0.PHPTUV2.Str.phsA - Stage 2 Start[.phsA] 10=Stage 2 phsA start 41 54 0 2 1 1
LD0.PHPTUV2.Str.phsB - Stage 2 Start[.phsB] 10=Stage 2 phsB start 41 55 0 2 1 1
LD0.PHPTUV2.Str.phsC - Stage 2 Start[.phsC] 10=Stage 2 phsC start 41 56 0 2 1 1
LD0.PHPTUV1.Str.phsA - Stage 1 Start[.phsA] 10=Stage 1 phsA start 41 64 0 2 1 1
LD0.PHPTUV1.Str.phsB - Stage 1 Start[.phsB] 10=Stage 1 phsB start 41 65 0 2 1 1
LD0.PHPTUV1.Str.phsC - Stage 1 Start[.phsC] 10=Stage 1 phsC start 41 66 0 2 1 1
LD0.PHPTUV1.Str.general PHPTUV1.START Stage 1 Start[.general] 10=Stage 1 start 41 84 1 2 1 1
LD0.PHPTUV1.Op.general PHPTUV1.OPERATE Stage 1 Operate[.general] 10=Stage 1 operate 41 90 1 2 0 1
LD0.PHPTUV2.Op.general PHPTUV2.OPERATE Stage 2 Operate[.general] 10=Stage 2 operate 41 91 1 2 0 1
LD0.PHPTUV2.Str.general PHPTUV2.START Stage 2 Start[.general] 10=Stage 2 start 41 94 1 2 1 1
LD0.PHPTUV3.Str.general PHPTUV3.START Stage 3 Start[.general] 10=Stage 3 start 41 96 1 2 1 1
LD0.PHPTUV3.Op.general PHPTUV3.OPERATE Stage 3 Operate[.general] 10=Stage 3 operate 41 98 1 2 0 1
Positive sequence undervoltage protection (1 stage), FE06,07
LD0.PSPTUV1.Str.phsA - Start[.phsA] 10=phsA start 42 64 0 2 1 1
LD0.PSPTUV1.Str.phsB - Start[.phsB] 10=phsB start 42 65 0 2 1 1
LD0.PSPTUV1.Str.phsC - Start[.phsC] 10=phsC start 42 66 0 2 1 1
LD0.PSPTUV1.Str.general PSPTUV1.START Start[.general] 10=Start 42 84 1 2 1 1
LD0.PSPTUV1.Op.general PSPTUV1.OPERATE Operate[.general] 10=Operate 42 90 1 2 0 1
Negative sequence overvoltage protection (1 stage), FE06,07
LD0.NSPTOV1.Str.phsA - Start[.phsA] 10=phsA start 43 64 0 2 1 1
LD0.NSPTOV1.Str.phsB - Start[.phsB] 10=phsB start 43 65 0 2 1 1
LD0.NSPTOV1.Str.phsC - Start[.phsC] 10=phsC start 43 66 0 2 1 1
LD0.NSPTOV1.Str.general NSPTOV1.START Start[.general] 10=Start 43 84 1 2 1 1
LD0.NSPTOV1.Op.general NSPTOV1.OPERATE Operate[.general] 10=Operate 43 90 1 2 0 1
Residual overvoltage protection (3 stages), FE06,07
LD0.ROVPTOV1.Str.general ROVPTOV1.START Stage 1 Start 10=Stage 1 start 44 84 1 2 1 1
LD0.ROVPTOV1.Op.general ROVPTOV1.OPERATE Stage 1 Operate 10=Stage 1 operate 44 90 1 2 0 1
LD0.ROVPTOV2.Op.general ROVPTOV2.OPERATE Stage 2 Operate 10=Stage 2 operate 44 91 1 2 0 1
LD0.ROVPTOV2.Str.general ROVPTOV2.START Stage 2 Start 10=Stage 2 start 44 94 1 2 1 1
LD0.ROVPTOV3.Str.general ROVPTOV3.START Stage 3 Start 10=Stage 3 start 44 96 1 2 1 1
LD0.ROVPTOV3.Op.general ROVPTOV3.OPERATE Stage 3 Operate 10=Stage 3 operate 44 98 1 2 0 1
Physical binary I/O signals
LD0.XGGIO130.Ind1.stVal - X130-Input 1 10=ON, 01=OFF 50 1 0 1 1 1
LD0.XGGIO130.Ind2.stVal - X130-Input 2 10=ON, 01=OFF 50 2 0 1 1 1
Table continues on next page
1MRS756712 C Section 2
IEC 60870-5-103 data mappings
REF615 17