IEC 61850 name AFL-Common SA name Description DPI value FUN INF In Use ASDU GI Coding
LD0.XGGIO130.Ind3.stVal - X130-Input 3 10=ON, 01=OFF 50 3 0 1 1 1
LD0.XGGIO130.Ind4.stVal - X130-Input 4 10=ON, 01=OFF 50 4 0 1 1 1
LD0.XGGIO130.Ind5.stVal - X130-Input 5 10=ON, 01=OFF 50 5 0 1 1 1
LD0.XGGIO130.Ind6.stVal - X130-Input 6 10=ON, 01=OFF 50 6 0 1 1 1
LD0.XGGIO130.SPCSO1.stVal - X130-Output 1 10=ON, 01=OFF 50 101 0 1 1 1
LD0.XGGIO130.SPCSO2.stVal - X130-Output 2 10=ON, 01=OFF 50 102 0 1 1 1
LD0.XGGIO130.SPCSO3.stVal - X130-Output 3 10=ON, 01=OFF 50 103 0 1 1 1
LD0.XGGIO120.Ind1.stVal - X120-Input 1 10=ON, 01=OFF 51 1 0 1 1 1
LD0.XGGIO120.Ind2.stVal - X120-Input 2 10=ON, 01=OFF 51 2 0 1 1 1
LD0.XGGIO120.Ind3.stVal - X120-Input 3 10=ON, 01=OFF 51 3 0 1 1 1
LD0.XGGIO120.Ind4.stVal - X120-Input 4 10=ON, 01=OFF 51 4 0 1 1 1
LD0.XGGIO110.Ind1.stVal - X110-Input 1 10=ON, 01=OFF 52 1 0 1 1 1
LD0.XGGIO110.Ind2.stVal - X110-Input 2 10=ON, 01=OFF 52 2 0 1 1 1
LD0.XGGIO110.Ind3.stVal - X110-Input 3 10=ON, 01=OFF 52 3 0 1 1 1
LD0.XGGIO110.Ind4.stVal - X110-Input 4 10=ON, 01=OFF 52 4 0 1 1 1
LD0.XGGIO110.Ind5.stVal - X110-Input 5 10=ON, 01=OFF 52 5 0 1 1 1
LD0.XGGIO110.Ind6.stVal - X110-Input 6 10=ON, 01=OFF 52 6 0 1 1 1
LD0.XGGIO110.Ind7.stVal - X110-Input 7 10=ON, 01=OFF 52 7 0 1 1 1
LD0.XGGIO110.Ind8.stVal - X110-Input 8 10=ON, 01=OFF 52 8 0 1 1 1
LD0.XGGIO110.SPCSO1.stVal - X110-Output 1 10=ON, 01=OFF 52 101 0 1 1 1
LD0.XGGIO110.SPCSO2.stVal - X110-Output 2 10=ON, 01=OFF 52 102 0 1 1 1
LD0.XGGIO110.SPCSO3.stVal - X110-Output 3 10=ON, 01=OFF 52 103 0 1 1 1
LD0.XGGIO110.SPCSO4.stVal - X110-Output 4 10=ON, 01=OFF 52 104 0 1 1 1
LD0.XGGIO100.SPCSO1.stVal - X100-Output 1 10=ON, 01=OFF 53 101 0 1 1 1
LD0.XGGIO100.SPCSO2.stVal - X100-Output 2 10=ON, 01=OFF 53 102 0 1 1 1
LD0.XGGIO100.SPCSO3.stVal - X100-Output 3 10=ON, 01=OFF 53 103 0 1 1 1
LD0.XGGIO100.SPCSO4.stVal - X100-Output 4 10=ON, 01=OFF 53 104 0 1 1 1
LD0.XGGIO100.SPCSO5.stVal - X100-Output 5 10=ON, 01=OFF 53 105 0 1 1 1
LD0.XGGIO100.SPCSO6.stVal - X100-Output 6 10=ON, 01=OFF 53 106 0 1 1 1
LD0.XAGGIO130.Ind1.stVal - XA130-Input 1 10=ON, 01=OFF 54 1 0 1 1 1
LD0.XAGGIO130.Ind2.stVal - XA130-Input 2 10=ON, 01=OFF 54 2 0 1 1 1
LD0.XAGGIO130.Ind3.stVal - XA130-Input 3 10=ON, 01=OFF 54 3 0 1 1 1
LD0.XAGGIO130.Ind4.stVal - XA130-Input 4 10=ON, 01=OFF 54 4 0 1 1 1
Arc protection (3 stages), optional in all variants
LD0.ARCSARC11.FADet.stVal ARCSARC1.ARC_FLT_DE
T
Stage1 Fault arc detected 10=Stage1 arc detected 156 211 1 1 0 1
LD0.ARCPTRC11.Op.general ARCSARC1.OPERATE Stage1 Operate 10=Stage1 operate 156 213 1 2 0 1
LD0.ARCSARC21.FADet.stVal ARCSARC2.ARC_FLT_DE
T
Stage2 Fault arc detected 10=Stage2 arc detected 156 221 1 1 0 1
LD0.ARCPTRC21.Op.general ARCSARC2.OPERATE Stage2 Operate 10=Stage2 operate 156 223 1 2 0 1
Table continues on next page
Section 2 1MRS756712 C
IEC 60870-5-103 data mappings
18 REF615
Point List Manual