IEC 61850 name AFL-Common SA name Description DPI value FUN INF In Use ASDU GI Coding
LD0.ARCSARC31.FADet.stVal ARCSARC3.ARC_FLT_DE
T
Stage3 Fault arc detected 10=Stage3 arc detected 156 231 1 1 0 1
LD0.ARCPTRC31.Op.general ARCSARC3.OPERATE Stage3 Operate 10=Stage3 operate 156 233 1 2 0 1
Phase discontinuity protection (1 stage), all variants
LD0.PDNSPTOC1.Str.general PDNSPTOC1.START Start 10=Stage start 157 84 1 2 1 1
LD0.PDNSPTOC1.Op.general PDNSPTOC1.OPERATE Operate 10=Stage operate 157 90 1 2 0 1
Transient/intermittent earth-fault protection (1 stage), FE01,02,05,06
LD0.INTRPTEF1.Str.general INTRPTEF1.START Start 10=Stage start 158 84 1 2 1 1
LD0.INTRPTEF1.Op.general INTRPTEF1.OPERATE Operate 10=Stage operate 158 90 1 2 0 1
Non-directional earth-fault and sensitive earth-fault protection (4 stages), partly supported in all variants, full support in FE03,04
LD0.EFLPTOC1.Str.general EFLPTOC1.START Low(1) stage start 10=Low(1) stage start 159 84 1 2 1 1
LD0.EFLPTOC1.Op.general EFLPTOC1.OPERATE Low(1) stage operate 10=Low(1) stage operate 159 90 1 2 0 1
LD0.EFLPTOC2.Op.general EFLPTOC2.OPERATE Low(2) stage operate 10=Low(2) stage operate 159 91 1 2 0 1
LD0.EFLPTOC2.Str.general EFLPTOC2.START Low(2) stage start 10=Low(2) stage start 159 94 1 2 1 1
LD0.EFHPTOC1.Str.general EFHPTOC1.START High stage start 10=High stage start 159 96 1 2 1 1
LD0.EFIPTOC1.Str.general EFIPTOC1.START Instanteous stage start 10=Instanteous stage start 159 97 1 2 1 1
LD0.EFHPTOC1.Op.general EFHPTOC1.OPERATE High stage operate 10=High stage operate 159 98 1 2 0 1
LD0.EFIPTOC1.Op.general EFIPTOC1.OPERATE Instanteous stage operate 10=Instanteous stage operate 159 99 1 2 0 1
Phase overcurrent protection (4 stages), FE01,02,03,04,05
LD0.PHIPTOC1.Str.phsA - Instanteous stage Start[.phsA] 10=Inst. stage phsA start 162 34 0 2 1 1
LD0.PHIPTOC1.Str.phsB - Instanteous stage Start[.phsB] 10=Inst. stage phsB start 162 35 0 2 1 1
LD0.PHIPTOC1.Str.phsC - Instanteous stage Start[.phsC] 10=Inst. stage phsC start 162 36 0 2 1 1
LD0.PHHPTOC2.Str.phsA - High(2) stage Start[.phsA] 10=High(2) stage phsA start 162 44 0 2 1 1
LD0.PHHPTOC2.Str.phsB - High(2) stage Start[.phsB] 10=High(2) stage phsB start 162 45 0 2 1 1
LD0.PHHPTOC2.Str.phsC - High(2) stage Start[.phsC] 10=High(2) stage phsC start 162 46 0 2 1 1
LD0.PHHPTOC1.Str.phsA - High(1) stage Start[.phsA] 10=High(1) stage phsA start 162 54 0 2 1 1
LD0.PHHPTOC1.Str.phsB - High(1) stage Start[.phsB] 10=High(1) stage phsB start 162 55 0 2 1 1
LD0.PHHPTOC1.Str.phsC - High(1) stage Start[.phsC] 10=High(1) stage phsC start 162 56 0 2 1 1
LD0.PHLPTOC1.Str.phsA - Low stage Start[.phsA] 10=Low stage phsA start 162 64 0 2 1 1
LD0.PHLPTOC1.Str.phsB - Low stage Start[.phsB] 10=Low stage phsB start 162 65 0 2 1 1
LD0.PHLPTOC1.Str.phsC - Low stage Start[.phsC] 10=Low stage phsC start 162 66 0 2 1 1
LD0.PHLPTOC1.Str.general PHLPTOC1.START Low stage Start[.general] 10=Low stage start 162 84 1 2 1 1
LD0.PHLPTOC1.Op.general PHLPTOC1.OPERATE Low stage Operate[.general] 10=Low stage operate 162 90 1 2 0 1
LD0.PHHPTOC1.Op.general PHHPTOC1.OPERATE High(1) stage Operate[.general] 10=High(1) stage operate 162 91 1 2 0 1
LD0.PHHPTOC1.Str.general PHHPTOC1.START High(1) stage Start[.general] 10=High(1) stage start 162 94 1 2 1 1
LD0.PHHPTOC2.Str.general PHHPTOC2.START High(2) stage Start[.general] 10=High(2) stage start 162 96 1 2 1 1
LD0.PHIPTOC1.Str.general PHIPTOC1.START Instanteous stage Start[.general] 10=Instanteous stage start 162 97 1 2 1 1
LD0.PHHPTOC2.Op.general PHHPTOC2.OPERATE High(2) stage Operate[.general] 10=High(2) stage operate 162 98 1 2 0 1
LD0.PHIPTOC1.Op.general PHIPTOC1.OPERATE Instanteous stage
Operate[.general]
10=Instanteous stage operate 162 99 1 2 0 1
Table continues on next page
1MRS756712 C Section 2
IEC 60870-5-103 data mappings
REF615 19