IEC 61850 name AFL-Common SA name Description DPI value FUN INF In Use ASDU GI Coding
Directional earth-fault protection (3 stages), FE01,02,05,06, 07
LD0.DEFLPTOC1.Str.general DEFLPDEF1.START Low(1) stage start 10=Low(1) stage start 163 84 1 2 1 1
LD0.DEFLPTOC1.Op.general DEFLPDEF1.OPERATE Low(1) stage operate 10=Low(1) stage operate 163 90 1 2 0 1
LD0.DEFLPTOC2.Op.general DEFLPDEF2.OPERATE Low(2) stage operate 10=Low(2) stage operate 163 91 1 2 0 1
LD0.DEFLPTOC2.Str.general DEFLPDEF2.START Low(2) stage start 10=Low(2) stage start 163 94 1 2 1 1
LD0.DEFHPTOC1.Str.general DEFHPDEF1.START High stage start 10=High stage start 163 96 1 2 1 1
LD0.DEFHPTOC1.Op.general DEFHPDEF1.OPERATE High stage operate 10=High stage operate 163 98 1 2 0 1
Three-phase inrush detection, all variants
LD0.INRPHAR1.Str.phsA - Start[.phsA] 10=Start phsA 167 64 0 2 1 1
LD0.INRPHAR1.Str.phsB - Start[.phsB] 10=Start phsB 167 65 0 2 1 1
LD0.INRPHAR1.Str.phsC - Start[.phsC] 10=Start phsC 167 66 0 2 1 1
LD0.INRPHAR1.Str.general - Start[.general] 10=Start general 167 84 1 2 1 1
Thermal overload protection, all variants
LD0.T1PTTR1.Str.general T1PTTR1.START Start 10=Start 168 84 1 2 1 1
LD0.T1PTTR1.AlmThm.general T1PTTR1.ALARM Thermal alarm 10=Thermal alarm 168 85 1 2 1 1
LD0.T1PTTR1.Op.general T1PTTR1.OPERATE Operate 10=Operate 168 90 1 2 0 1
Auto-reclosing, optional in all variants
LD0.DARREC1.RsRec.ctlVal - AR reset 10=Reset 169 19 1 20 0 1
LD0.DARREC1.RsCnt.ctlVal - AR counters reset 10=Reset 169 20 1 20 0 1
LD0.DARREC1.PrgRec1.stVal DARREC1.INPRO_1 AR in progress 1st reclose 10=In progress 169 101 1 2 0 1
LD0.DARREC1.PrgRec2.stVal DARREC1.INPRO_2 AR in progress 2nd reclose 10=In progress 169 102 1 2 0 1
LD0.DARREC1.PrgRec3.stVal DARREC1.INPRO_3 AR in progress 3rd reclose 10=In progress 169 103 1 2 0 1
LD0.DARREC1.PrgRec4.stVal DARREC1.INPRO_4 AR in progress 4th reclose 10=In progress 169 104 1 2 0 1
LD0.DARREC1.PrgRec5.stVal DARREC1.INPRO_5 AR in progress 5th reclose 10=In progress 169 105 1 2 0 1
LD0.DARREC1.PrgRec.stVal DARREC1.INPRO AR in progress 10=In progress 169 120 1 2 0 1
LD0.DARREC1.CBManCls.stVal DARREC1.MAN_CB_CL CB manually closed 10=CB manually closed 169 159 1 2 0 1
LD0.DARREC1.LO.stVal DARREC1.LOCKED Lockout status 10=Lockout 169 164 1 2 0 1
LD0.DARREC1.UnsRec.stVal DARREC1.UNSUC_RECL Unsuccessful reclose status 10=Unsuccessful reclose 169 170 1 2 0 1
LD0.DARREC1.InBlkThm.stVal - Thermal block (status) 10=Thermal block 169 171 1 2 0 1
LD0.DARREC1.RdyRec.stVal DARREC1.READY Ready reclose status 10=Reclose ready 169 172 1 2 0 1
LD0.DARREC1.ActRec.stVal DARREC1.ACTIVE Active reclose status 10=Reclose active 169 173 1 2 0 1
LD0.DARREC1.PrgDsr.stVal DARREC1.DISCR_INPRO Discrimination time in progress 10=Discrimination time in progress 169 174 1 2 0 1
LD0.DARREC1.PrgCutOut.stVal DARREC1.CUTOUT_INPR
O
Cutout time in progress 10=Cutout time in progress 169 175 1 2 0 1
LD0.DARREC1.FrqOpAlm.stVal DARREC1.FRQ_OP_ALM Frequent operation counter alarm 10=Frequent operation alarm 169 176 1 2 0 1
LD0.DARREC1.RclTmStr.stVal - Reclaim time started 10=Reclaim time started 169 177 1 2 0 1
LD0.DARREC1.ProCrd.stVal - Protection coordination 10=Protection coordination 169 178 1 2 0 1
LD0.DARREC1.Op.general DARREC1.CLOSE_CB Operate (close command to
XCBR)
10=Close command to CB 169 179 1 2 0 1
Table continues on next page
Section 2 1MRS756712 C
IEC 60870-5-103 data mappings
20 REF615
Point List Manual