IEC 61850 name AFL-Common SA name Description DPI value FUN INF In Use ASDU GI Coding
LD0.DARREC1.OpOpn.general DARREC1.OPEN_CB Operate (open command to
XCBR)
10=Open command to CB 169 180 1 2 0 1
LD0.DARREC1.UnsCBCls.stVal DARREC1.UNSUC_CB Unsuccessful CB closing status 10=Unsuccessful CB closing 169 181 1 2 0 1
LD0.DARREC1.WtMstr.stVal DARREC1.CMD_WAIT Master signal to follower 10=Master signal to follower 169 182 1 2 0 1
Phase currents limit supervision, all variants
LD0.CMMXU1.HiAlm.stVal CMMXU1.HIGH_ALARM High alarm 10=High alarm 210 1 0 1 1 1
LD0.CMMXU1.HiWrn.stVal CMMXU1.HIGH_WARN High warning 10=High warning 210 2 0 1 1 1
LD0.CMMXU1.LoWrn.stVal CMMXU1.LOW_WARN Low warning 10=Low warning 210 3 0 1 1 1
LD0.CMMXU1.LoAlm.stVal CMMXU1.LOW_ALARM Low alarm 10=Low alarm 210 4 0 1 1 1
Residual current limit supervision, all variants
LD0.RESCMMXU1.HiAlm.stVal RESCMMXU1.HIGH_ALAR
M
High alarm 10=High alarm 210 11 0 1 1 1
LD0.RESCMMXU1.HiWrn.stVal RESCMMXU1.HIGH_WAR
N
High warning 10=High warning 210 12 0 1 1 1
Phase-to-phase voltage limit supervision, FE05,06,07
LD0.VMMXU1.HiAlm.stVal VMMXU1.HIGH_ALARM High alarm 10=High alarm 211 1 0 1 1 1
LD0.VMMXU1.HiWrn.stVal VMMXU1.HIGH_WARN High warning 10=High warning 211 2 0 1 1 1
LD0.VMMXU1.LoWrn.stVal VMMXU1.LOW_WARN Low warning 10=Low warning 211 3 0 1 1 1
LD0.VMMXU1.LoAlm.stVal VMMXU1.LOW_ALARM Low alarm 10=Low alarm 211 4 0 1 1 1
Residual voltage limit supervision, FE01,02,05,06,07
LD0.RESVMMXU1.HiAlm.stVal RESVMMXU1.HIGH_ALAR
M
High alarm 10=High alarm 211 11 0 1 1 1
LD0.RESVMMXU1.HiWrn.stVal RESVMMXU1.HIGH_WAR
N
High warning 10=High warning 211 12 0 1 1 1
Circuit breaker position and failure protection, all variants
CTRL.CBCILO1.EnaOpn.stVal CBXCBR1.ENA_OPEN CB open enabled 10=Open enabled 240 21 1 1 1 1
CTRL.CBCILO1.EnaCls.stVal CBXCBR1.ENA_CLOSE CB close enabled 10=Close enabled 240 22 1 1 1 1
CTRL.CBXCBR1.BlkOpn.stVal CBXCBR1.BLK_OPEN CB open blocked 10=Open blocked 240 23 1 1 1 1
CTRL.CBXCBR1.BlkCls.stVal CBXCBR1.BLK_CLOSE CB close blocked 10=Close blocked 240 24 1 1 1 1
CTRL.CCBRBRF1.Str.general CCBRBRF1.CB_FAULT_AL Start, timer running 10=Start,timer running 240 101 0 2 1 1
CTRL.CCBRBRF1.OpEx.general CCBRBRF1.TRBU Failure, external trip 10=Failure,external trip 240 102 0 2 0 1
CTRL.CCBRBRF1.OpIn.general CCBRBRF1.TRRET Operate, internal retrip 10=Operate, internal re-trip 240 103 0 2 0 1
CTRL.CBCSWI1.Pos.stVal CBXCBR1.POSITION Circuit breaker position 10=Close;01=Open;00=Intermediate;
11=Error
240 160 1 1,20 1 2
Circuit breaker condition monitoring, FE02,04,05,06,07
LD0.SSCBR1.RsAccAPwr.ctlVal SSCBR1.RST_IPOW Reset accumulation energy 10=Reset 242 19 1 20 0 1
LD0.SSCBR1.RsCBWear.ctlVal SSCBR1.RST_CB_WEAR Reset CB remaining life and
op.counters
10=Reset 242 20 1 20 0 1
LD0.SSCBR1.RsTrvTm.ctlVal SSCBR1.RST_TRV_T Reset CB travelling time alarm 10=Reset 242 21 1 20 0 1
LD0.SSCBR1.RsSprChaTm.ctlVal SSCBR1.RST_SPR_T Reset CB spring charge time
alarm
10=Reset 242 22 1 20 0 1
LD0.SSCBR1.OpnAlm.stVal SSCBR1.TRV_T_OP_ALM Open travel time exceeded 10=Open travel time alarm 242 101 0 1 0 1