3.11.3 Signals
Table 55: X130 (RTD/mA) analog input signals
Name Type Description
ALARM BOOLEAN General alarm
WARNING BOOLEAN General warning
AI_VAL1 FLOAT32 mA input, Connectors 1-2, instantaneous value
AI_VAL2 FLOAT32 mA input, Connectors 3-4, instantaneous value
AI_VAL3 FLOAT32 RTD input, Connectors 5-6-11c, instantaneous
value
AI_VAL4 FLOAT32 RTD input, Connectors 7-8-11c, instantaneous
value
AI_VAL5 FLOAT32 RTD input, Connectors 9-10-11c, instantaneous
value
AI_VAL6 FLOAT32 RTD input, Connectors 13-14-12c, instantaneous
value
AI_VAL7 FLOAT32 RTD input, Connectors 15-16-12c, instantaneous
value
AI_VAL8 FLOAT32 RTD input, Connectors 17-18-12c, instantaneous
value
3.11.4 Settings
Table 56: RTD input settings
Parameter
Values (Range) Unit Step Default Description
Input mode 1=Not in use
2=Resistance
10=Pt100
11=Pt250
20=Ni100
21=Ni120
22=Ni250
30=Cu10
1=Not in use Analogue input mode
Input maximum 0...2000 1 2000 Maximum analogue input value for mA
or resistance scaling
Input minimum 0...2000 1 0 Minimum analogue input value for mA or
resistance scaling
Value unit 1=Dimensionless
5=Ampere
23=Degrees
celsius
30=Ohm
1=Dimensionless Selected unit for output value format
Value maximum -10000.0...10000.0 10000.0 Maximum output value for scaling and
supervision
Value minimum -10000.0...10000.0 -10000.0 Minimum output value for scaling and
supervision
Val high high limit -10000.0...10000.0 10000.0 Output value high alarm limit for
supervision
Table continues on next page