Functionality IEC 61850 IEC 60617 ANSI
Motor startup supervision STTPMSU Is2t n< 49,66,48,51LR
Negative phase-sequence time overcurrent
protection
MNSPTOC I
2
>M 46M
Three-phase overvoltage PHPTOV 3U> 59
Three-phase undervoltage PHPTUV 3U< 27
Positive-sequence overvoltage PSPTOV U
1
> 47O+
Positive-sequence undervoltage PSPTUV U
1
< 47U+
Negative-sequence overvoltage NSPTOV U
2
> 47O-
Residual overvoltage ROVPTOV U
0
> 59G
Frequency gradient DAPFRC df/dt> 81R
Overfrequency DAPTOF f> 81O
Underfrequency DAPTUF f< 81U
Circuit-breaker failure CCBRBRF 3I>/I
0
>BF 51BF/51NBF
Tripping logic TRPPTRC I → O 94/86
Control
Bay control QCCBAY CBAY CBAY
Interlocking interface SCILO 3 3
Circuit-breaker/disconnector control GNRLCSWI I ↔ O CB/DC I ↔ O CB/DC
Circuit breaker DAXCBR I ↔ O CB I ↔ O CB
Disconnector DAXSWI I ↔ O DC I ↔ O DC
Local/remote switch interface LOCREM R/L R/L
Supervision and monitoring
Circuit-breaker condition monitoring SSCBR CBCM CBCM
Fuse failure supervision SEQRFUF FUSEF 60
Current-circuit supervision CCRDIF MCS 3I MCS 3I
Trip-circuit supervision TCSSCBR TCS TCM
Generic measured values MVGGIO
Measured value limit supervision MVEXP
Station battery supervision SPVNZBAT U<> U<>
Energy monitoring EPDMMTR E E
Measurement
Three-phase current CMMXU 3I 3I
Three-phase voltage, phase-to-earth
voltages (RMS)
VPHMMXU 3Upe 3Upe
Three-phase voltage, phase-to-phase
voltages (RMS)
VPPMMXU 3Upp 3Upp
Residual current RESCMMXU I
0
I
0
Residual voltage RESVMMXU U
0
V
n
Sequence current CSMSQI I
1
,I
2
I
1
,I
2
Sequence voltage VSMSQI U
1
,U
2
V
1
,V
2
Table continues on next page
Section 1 1MRS756785 A
Introduction
8 REM630
Application Manual