Table 8: Interface of binary outputs
Hardware module instance Hardware channel Description
PSM BO1_PO Master Trip 1
PSM BO2_PO Motor start
PSM BO3_PO Master Trip 2
PSM BO4_PO Restart enable
PSM BO5_PO Backup trip
PSM BO6_PO Not connected
PSM BO7_SO Common operate
PSM BO8_SO Common start
PSM BO9_SO Motor startup
The IED measures the analog signals needed for protection and measuring
functions via galvanically isolated matching transformers. The matching
transformer input channels 1…4 are intended for current measuring and channels
7...10 for voltage measuring.
Table 9: Interface of analog inputs
Hardware module instance
Hardware channel Description
AIM_2 CH1 Phase current IL1
AIM_2 CH2 Phase current IL2
AIM_2 CH3 Phase current IL3
AIM_2 CH4
Neutral current I
0
AIM_2 CH5 Not connected
AIM_2 CH6 Not available
AIM_2 CH7 Phase voltage UL1
AIM_2 CH8 Phase voltage UL2
AIM_2 CH9 Phase voltage UL3
AIM_2 CH10
Neutral voltage U
0
3.2.4 Preprocessing blocks and fixed signals
The analog current and voltage signals coming to the IED are processed by
preprocessing blocks. There are two types of preprocessing blocks based on 20
samples per cycle and 80 samples per cycle. All function blocks functioning at 5
ms task time need 80 samples per cycle whereas all the rest need 20 samples per cycle.
A fixed signal block providing a logical TRUE and a logical FALSE output has
been used. Outputs are connected internally to other functional blocks when needed.
1MRS756785 A Section 3