1.4.2 Manual conventions
Conventions used in IED manuals. A particular convention may not be used in this
manual.
Abbreviations and acronyms in this manual are spelled out in Glossary.
Glossary also contains definitions of important terms.
Push button navigation in the LHMI menu structure is presented by using the
push button icons, for example:
To navigate between the options, use
and .
HMI menu paths are presented in bold, for example:
Select Main menu/Settings.
LHMI messages are shown in Courier font, for example:
To save the changes in non-volatile memory, select Yes and press .
Parameter names are shown in italics, for example:
The function can be enabled and disabled with the Operation setting.
The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set an own signal name
in PCM600.
The * character after an input or output signal name in the function block
symbol given for a function, indicates that the signal must be connected to
another function block in the application configuration to achieve a valid
application configuration.
1.4.3 Functions, codes and symbols
Table 1: Functions included in REM630
Functionality
IEC 61850 IEC 60617 ANSI
Protection
Three-phase non-directional overcurrent,
low stage
PHLPTOC 3I> 51P-1
Three-phase non-directional overcurrent,
instantaneous stage
PHIPTOC 3I>>> 50P/51P
Non-directional earth fault, low stage EFLPTOC I
0
> 51N-1
Non-directional earth fault, high stage EFHPTOC I
0
>> 51N-2
Non-directional earth fault, instantaneous
stage
EFIPTOC I
0
>>> 50N/51N
Directional earth fault, low stage DEFLPDEF I
0
> → 67N-1
Directional earth fault, high stage DEFHPDEF I
0
>> → 67N-2
Phase reversal PREVPTOC I
2
>> 46R
Three-phase thermal overload for motors MPTTR 3Ith>M 49M
Loss-of-load supervision LOFLPTUC 3I< 37
Motor stall protection JAMPTOC Ist> 51LR
Emergency start ESMGAPC ESTART ESTART
Table continues on next page
1MRS756785 A Section 1
Introduction
REM630 7
Application Manual

Table of Contents