Table 60. Event recorder DRPRDRE
Function Value
Buffer capacity Maximum number of events in disturbance report 150
Maximum number of disturbance reports 100
Resolution 1 ms
Accuracy Depending on time
synchronizing
Table 61. Trip value recorder DRPRDRE
Function Value
Buffer capacity
Maximum number of analog inputs 30
Maximum number of disturbance reports 100
Table 62. Disturbance recorder DRPRDRE
Function Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 96
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
Table 63. Station battery supervision SPVNZBAT
Function
Range or value Accuracy
Lower limit for the battery terminal
voltage
(60-140) % of Ubat ± 1.0% of set battery voltage
Reset ratio, lower limit <105 % -
Upper limit for the battery terminal
voltage
(60-140) % of Ubat ± 1.0% of set battery voltage
Reset ratio, upper limit >95 % -
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Table 64. Insulation gas monitoring function SSIMG
Function
Range or value Accuracy
Pressure alarm 0.00-25.00 -
Pressure lockout 0.00-25.00 -
Temperature alarm -40.00-200.00 -
Temperature lockout -40.00-200.00 -
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Breaker protection REQ650 1MRK 505 283-BEN -