Table 65. Insulation liquid monitoring function SSIML
Function Range or value Accuracy
Alarm, oil level 0.00-25.00 -
Oil level lockout 0.00-25.00 -
Temperature alarm -40.00-200.00 -
Temperature lockout -40.00-200.00 -
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Table 66. Circuit breaker condition monitoring SSCBR
Function Range or value Accuracy
Alarm levels for open and close travel
time
(0-200) ms ± 0.5% ± 25 ms
Alarm levels for number of operations (0 - 9999) -
Setting of alarm for spring charging
time
(0.00-60.00) s ± 0.5% ± 25 ms
Time delay for gas pressure alarm (0.00-60.00) s ± 0.5% ± 25 ms
Time delay for gas pressure lockout (0.00-60.00) s ± 0.5% ± 25 ms
Metering
Table 67. Pulse counter PCGGIO
Function
Setting range Accuracy
Cycle time for report of counter
value
(1–3600) s -
Table 68. Function for energy calculation and demand handling ETPMMTR
Function
Range or value Accuracy
Energy metering MWh Export/Import, MVArh
Export/Import
Input from MMXU. No extra error at steady load
Breaker protection REQ650 1MRK 505 283-BEN -
Product version: 1.2
80 ABB