2.4.29 LD0.VMSTA2 Voltage demand values (2)
Table 120: LD0.VMSTA2 Voltage demand values (2)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.VMSTA Demand phase-to-ground
1928 u16 1000 .AvVPhsA.mag U_DMD_A - phsA amplitude 0...4.0 [xUn]
1929 u16 1000 .AvVPhsB.mag U_DMD_B - phsB amplitude 0...4.0 [xUn]
1930 u16 1000 .AvVPhsC.mag U_DMD_C - phsC amplitude 0...4.0 [xUn]
. Demand phase-to-phase
1931 u16 1000 .AvVPhsAB.mag U_DMD_AB - phsAB amplitude 0...4.0 [xUn]
1932 u16 1000 .AvVPhsBC.mag U_DMD_BC - phsBC amplitude 0...4.0 [xUn]
1933 u16 1000 .AvVPhsCA.mag U_DMD_CA - phsCA amplitude 0...4.0 [xUn]
Update timestamp
1)
1934 u16 - - Year - Month
1935 u16 - - Day - Hour
1936 u16 - - Minute - Second
1937 u16 - - Millisecond
1938 u16 - - Time quality
1) See the technical manual.
2.4.30 LD0.PEMSTA1 Power measurement demand values (1)
Table 121: LD0.PEMSTA1 Power measurement demand values (1)
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.PEMSTA1 Demand
1939 i32 1 .AvW.mag - Active power P (high) -/+ 999,999
1940 - (low word)
1941 i32 1 .AvVAr.mag - Reactive power Q (high) -/+ 999,999
1942 - (low word)
1943 i32 1 .AvVA.mag - Apparent power S (high) -/+ 999,999
1944 - (low word)
1945 i16 1000 .AvPF.mag - Power factor -1...1
1946 < reserved > 0
Max values:
1947 i32 1 .MaxW.mag - Active power P (high) -/+ 999,999
1948 - (low word)
1949 i32 1 .MaxVAr.mag - Reactive power Q (high) -/+ 999,999
1950 - (low word)
1951 i32 1 .MaxVA.mag - Apparent power S (high) -/+ 999,999
1952 - (low word)
1953 < reserved > 0