2.3.3 LD0.PHHPTOC1 Phase overcurrent protection, high stage
(1)
Table 6: LD0.PHHPTOC1 Phase overcurrent protection, high stage (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHHPTOC1
2890 180.10 .Str.general START General start 1=Start
2891 180.11 .mcd
2892 180.12 .Str.phsA phsA start 1=Start
2893 180.13 .mcd
2894 180.14 .Str.phsB phsB start 1=Start
2895 180.15 .mcd
2896 181.00 .Str.phsC phsC start 1=Start
2897 181.01 .mcd
2898 181.02 .Op.general OPERATE General operate 1=Operate
2899 181.03 .mcd
2.3.4 LD0.PHIPTOC1 Phase overcurrent protection,
instantaneous stage (1)
Table 7: LD0.PHIPTOC1 Phase overcurrent protection, instantaneous stage (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.PHIPTOC1
2910 181.14 .Str.general START General start 1=Start
2911 181.15 .mcd
2912 182.00 .Str.phsA phsA start 1=Start
2913 182.01 .mcd
2914 182.02 .Str.phsB phsB start 1=Start
2915 182.03 .mcd
2916 182.04 .Str.phsC phsC start 1=Start
2917 182.05 .mcd
2918 182.06 .Op.general OPERATE General operate 1=Operate
2919 182.07 .mcd
1MRS757822 B Section 2
Modbus data mappings
Recloser Protection and Control RER615 19
Point List Manual