ABB | SACE Emax 2
External electronic accessories
8 - Ekip Com IEC 61850
234 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Configurations via menu
Local bus activation, which is essential for starting the communication between module and Ekip Touch,
is available in the
Settings
menu (page 49).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the
Settings
-
Modules
menu:
Parameter Description Default
Static IP address ON
Defines whether the module has the dynamic (Off) or
static (On) IP address.
Se = On all the associated parameters are enabled
OFF
Static address IP address
Enables the static IP to be selected 0.0.0.0
Static Network Mask
Enables the subnet mask to be selected 0.0.0.0
Static Gateway address
When there are several subnets, enables the IP
address of the node to which the module is connected
to be selected
0.0.0.0
Enable SNTP client
Allows the SNTP protocol for distribution of the clock
and synchronization signal to be enabled.
OFF
SNTP Server Addr.
Allows the network server that supplies the SNTP to
be set.
0.0.0.0
Configuration Session
Defines the write mode of the configuration file in the
module via the TFTP port; two options are available:
• Always ON: the TFTP port is always open and write
is always enabled
• Activation requested: the TFTP is opened by a
specific command, which enables write for a limited
time (or for a finite number of data packages)
Always
ON
Start Configuration
Write enable command on TFTP port in Activation
mode requested
---
Information in menu
The following information will be available in the
About
-
Modules
menu if Ekip Touch has detected the
module correctly:
Information Description
SN and version
Identifier and SW version of the module
IP address
Address of the module, assigned to the module by a DHCP server at the
time of connection to the network in the case of configuration with a
dynamic IP, or can be set via the menu in the event of a static IP
NOTE:
without a DHCP server, the module automatically adopts a
random IP address within the 169.254.xxx.xxx
range
Network Mask
Subnet mask; identifies the method for recognizing the subnet to which
the modules belong and enables modules to be searched for within a
defined set of recipients.
Gateway address
IP address of the node to which the module is connected, in the presence
of several subnets
MAC address
Address assigned by ABB, with OUI (Organizationally Unique Identifier)
equal to ac:d3:64, which uniquely identifies the manufacturer of an
Ethernet device
Cfg file
Name of the configuration file uploaded to the modules
Cfg file error
Code of the error concerning the configuration file (0 = no error)