ABB | SACE Emax 2
116 | © 2013 ABB | 1SDH001000R0002 - L7804
Ekip Touch protection release | 12 - G Touch protections
Summary table for G Touch protections
ABB
ANSI
(5)
Threshold
Tolerance
threshold
Tripping time
Calculation
formula t
t
(2)
Tolerance t
t
(3)
S(V)
(Step)
51V
I20 = 0.6...10 In; Step = 0.1 In
Ul = 0.2…1 Un; Step = 0.01 Un
Ks = 0.1…1; Step = 0.01
± 10 %
t20 = 0.05…30 s
Step = 0.01 s
t
t
= t20
The better of the
two values:
± 10% or ± 40 ms
S(V)
(Linear)
51V
I20 = 0.6...10 In; Step = 0.1 In
Ul = 0.2…1 Un; Step = 0.01 Un
Uh = 0.2…1 Un; Step = 0.01 Un
Ks = 0.1…1; Step = 0.01
± 10 %
t20 = 0.05…30 s
Step = 0.01 s
t
t
= t20
(4)
The better of the
two values:
± 10% or ± 40 ms
RV 59N
U22 = 0.1….0.5 Un
Step = 0.001 Un
± 5 %
t22 = 0.5…60 s
Step = 0.05 s
t
t
= t22
The better of the
two values:
± 10% or ± 40 ms
RQ 40/32R
Q24 = -1…-0.1 Sn; Step = 0.001
Sn
Kq = -2…2; Step = 0.01
± 10 %
t24 = 0.5…100 s
Step = 0.1 s
t
t
= t24
The better of the
two values:
± 10% or ± 40 ms
OP 32OF
P26 = 0.4…2 Sn
Step = 0.001 Sn
± 10 %
t26 = 0.5…100 s
Step = 0.5 s
t
t
= t26
The better of the
two values:
± 10% or ± 40 ms
OQ 32OF
Q27 = 0.4…2 Sn
Step = 0.001 Sn
± 10 %
t27 = 0.5…100 s
Step = 0.5 s
t
t
= t27
The better of the
two values:
± 10% or ± 40 ms
UP 32LF
P23 = 0.1...1 Sn
Step = 0.001 Sn
± 10 %
t23 = 0.5…100 s
Step = 0.5 s
t
t
= t23
The better of the
two values:
± 10% or ± 40 ms
Table of Additional Functions of the protections
Protection UP has Startup Enable:
ABB
Time
(4)
UP(Startup)
t23
startup
= 0.1…30 s
step = 0.01 s
Notes
(1)
The calculation of t
t
is valid for values that have exceeded the activation threshold of the protection.
(2)
Valid tolerances with release energized in service conditions or with the auxiliary, tripping time = 100 ms, temperature and currents within operating
limits. If the conditions are not guaranteed, the tolerance of the tripping time becomes ± 20%.
(3)
The tripping threshold of the current for voltage values between Ul and Uh is calculated by performing the linear interpolation between the th-
resholds Uh and I20 (first point on the line) and Ul and Ks * I20 (second point on the line). I
threshold
= [(I20 * Ks *I20) / (Uh * Ul)] / (U
measured
* Uh) + I20.
(4)
The startup of protection UP is to be considered as the temporary deactivation time of the protection, starting from the exceeding of the startup
threshold.
(5)
ANSI / IEEE C37-2 encoding.