2TLC010062M0201 Rev.F 25
Test/start/reset interface specification
Applied voltage rating Minimum 5 VDC
Maximum 300 VDC
Response time
Delay at power on ≤ 40 ms
Response time at inactivation ≤ 20 ms
Electrical operations lifetime
Load Σ lth
2
≤ 64 AC1, AC15 160 000 operations
DC1, DC13 100 000 operations
Measurement conditions:
• Maximum breaking voltage for relay contacts: 250 V
• Maximum switching voltage for relay contacts: 400 V
• Rated current
• Switching frequency ≤ 0.1 Hz (Switching frequency > 0.1 Hz will shorten life.)
• T ≤ 55 °C
• No arc suppression (Usage of arc suppression will prolong life but may increase response
time at inactivation.)
• 3 phase load in a star connection.
Mechanical data
Weight 190 – 230 g
Material Housing PA66 with 25 % fiberglass
(UL94 V0)
Connection block, screw
compression type
PA66 (UL94 V0)
Connection block, push-in type PA66 with 25 % fiberglass
(UL94 V0)
Opener, push-in type PBT/GF (UL94 V0)
Color Housing Yellow
Connection block, screw
compression type
Black
Connection block, push-in type Black
Opener, push-in type Orange
Attachment requirements 35 mm DIN rail (DIN 50022)
Environmental data
Pollution degree II
Protection class Safety relay IP20
Enclosure for installation At least IP54. Lockable.
Ambient temperature range for operation within specified
operation range
-25°C – +55°C
Ambient temperature range for storage -40°C ≤Ta ≤ +70°C
Humidity range for operation 10 % ≤ Rh ≤ 90 %, no icing,
occasional condensation
Humidity range for storage 10 % ≤ Rh ≤ 95 %, no icing,
occasional condensation
Maximum temperature gradient 2°C/min