2TLC010062M0201 Rev.F 27
Approvals
CCC
RCM
S
KC
UKCA
Standard
IEC 61508 PFH
D
4.1E-9 and PFD 6.8E-6
EN ISO 13849-1, EN 62061 PFH
D
4.1E-9
Mission time 20 years
Information for use in USA/Canada
Intended use Applications according to NFPA 79
Power source A suitable isolating source in conjunction with
a fuse in accordance with UL248. The fuse
shall be rated max. 4 A and be installed in the
+24 VDC and 230VAC power supply to the
device in order to limit the available current.