EasyManua.ls Logo

ABB Tmax T8 L5757 - Mechanical Operating Mechanism Maintenance; Electrical and Mechanical Accessories Maintenance

ABB Tmax T8 L5757
39 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
L3692
Tmax T8
14/39
Doc N°
Mod.
Apparatus
Scale
Page N°
1SDH000682R0002
L3885
L5757
- If the undervoltage release is installed, disassemble the coil support and unload the springs of the operating mechanism by
closing and opening the circuit-breaker.
Fig. 20
8.3.5. Mechanical operating mechanism
- Clean the points indicated in fi gure 21. Use a cleaning product such as Henkel’s 273471 or equivalent if there is a heavy coat-
ing of dirt.
- Lubricate the opening and closing latches and the shafts in the points indicated in fi gure 21 with MOBILGREASE 28 (EXXON
MOBIL).
- Make sure that the opening and closing shafts are free to turn.
Fig. 21
8.3.6. Electrical and mechanical accessories
- Make sure that the accessories are securely fi xed to the circuit-breaker.
- Make sure that the electrical accessories are correctly connected to the circuit-breaker.
- Gearmotor: after every 10000 operations, check the brushes for wear and replace the gearmotor if necessary.
- Make sure that the releases (SOR-UVR-SRC) are in good conditions (absence of excessive wear, overheating, breakages) Fig. 22.
- Make sure that the mechanical operation counter functions correctly (if applicable) by operating the circuit-breaker.
2Nm
Fig. 22

Table of Contents