40 TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | CI/TTF300-EN REV. H
8 Commissioning
Communication
Operating modes
Point-to-point communication mode standard (general
address 0)
HART 5: Multidrop mode (addressing 1 to 15)
HART 7: Addressing 0 to 63, independent of current loop
mode
Burst Mode
Configuration options / tools
Driver-independent:
HMI LCD indicator with configuration function
Driver-dependent:
Device management / Asset management tools
FDT technology via TTX300-DTM driver
(Asset Vision Basic / DAT200)
EDD via TTX300 EDD driver
(Handheld terminal, Field Information Manager / FIM)
FDI technology via TTX300 FDI Device Package
(Field Information Manager / FIM)
Diagnosis notice
Overrange- / underrange in accordance with NE 43
HART® diagnosis
Extended from SW rev. 03.00:
Device status signaling according to NE 107
Freely configurable diagnostic categorization with
diagnostic history in accordance with NE 107
Tracking of events and configuration changes, from SW rev.
03.00
The HART® device stores information on critical events and
configuration changes.
The information can be output via tools:
Event monitor for the logging of critical events
Configuration monitor for configuration changes
For detailed information, see HART® COM/TTX300/HART
interface description.
PROFIBUS® Communication
Note
The PROFIBUS PA® protocol is an unsecured protocol, as such
the intended application should be assessed to ensure that
these protocols are suitable before implementation.
The interface conforms to Profile 3.01
(standard PROFIBU, EN 50170, DIN 1924 [PRO91]).
1
Transmitter
2
Bus termination
3
Segment coupler
4
PC / DCS
Figure 32: Example of PROFIBUS PA® interface connection
Manufacturer ID
0x1A
ID number
0x3470 [0x9700]
Profile
PA 3.01 (see PROFIBUS
PA® interface
description (COM/TTX300/PB))
Configuration
On device using LCD indicator
DTM
EDD
GSD
Transmission signal
IEC 61158-2
Voltage / current consumption
Average current consumption:12 mA.
In the event of an error, the FDE function (= Fault
Disconnection Electronic) integrated in the device makes
sure that the current consumption cannot exceed a
maximum of 20 mA.