42 TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | CI/TTF300-EN REV. H
9 Operation
Safety instructions
If there is a chance that safe operation is no longer possible,
take the device out of operation and secure it against
unintended startup.
Hardware settings
LCD indicator interface
DIP switch
Figure 34: DIP switch on the transmitter
(not for HART devices from HW - rev. 02.00)
Located on the top of the transmitter next to the LCD indicator
interface
1 are two DIP switches 2.
Switch 1 activates the hardware write protection.
Switch 2 supports the request of the FOUNDATION Fieldbus for
a hardware release for simulation in accordance with ITK.
For transmitters that support HART 7, switch 2 allows the
desired HART version to be set (HART 5 or HART 7).
Local write protection
Off: Local write protection deactivated
On: Local write protection activated
Release of the simulation
(FOUNDATION Fieldbus only)
deactivated
HART version
5
Note
• Factory setting: both switches set to ‘OFF’. Local write
protection deactivated and HART 5, unless explicitly ordered
HART 7 (HART version) or simulation locked (FOUNDATION
Fieldbus).
• In PROFIBUS PA devices, Switch 2 must always be set to the
‘OFF’ position.
Menu navigation
Operating buttons for menu
navigation
Indication of menu designation
Indication of menu number
Marking to indicate relative
position within the menu
Indication of the current function
assigned to the operating
buttons and
Figure 35: LCD display (example)
You can use the or operating buttons to browse through
the menu or select a number or character within a parameter
value.
Different functions can be assigned to the and operating
buttons. The function
5 that is currently assigned to them is
shown on the LCD display.
Control button functions
parameter entry
Select the next position for entering numerical and
alphanumeric values
/ parameter
Note
For detailed information on the parameterization of the device,
consult the associated operating instructions.