EasyManua.ls Logo

ABB TZID - Page 41

ABB TZID
67 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42/18-54 EN Electro-pneumatic positioner TZID 41
Environmental capabilities
Climate classe
GPF to DIN 40040
Ambient temperature
-40 °C to +85 °C for operation, storage and transport
-25 °C to +85 °C when using proximity switch SJ2-S1N (NO)
Explosion protection
ATEX II 2G EEx ia II C T6
Examination certificate TÜV 02 ATEX 1830 X
Type: Intrinsically safe
Device class: II 2G (EEx ia IIC)
Temperature class: T4, T5, T6
Permissible ambient temp.:T4: -40 °C T
amb.
85 °C
T5: -40 °C T
amb.
50 °C
T6: -40 °C T
amb.
35 °C
ATEX II 3G EEx n A II T6
Examination certificate TÜV 02 ATEX 1867 X
Type: Explosion-proof (Zone 2)
Device class: II 3G (EEx n A II)
Temperature class: T4, T5, T6
Permissible ambient temp.: T4: -40 °C T
amb.
85 °C
T5: -40 °C T
amb.
65 °C
T6: -40 °C T
amb.
50 °C
FM
Intrinsically safe CL I-II-III, Div 1, Grp A-B-C-D-E-F-G
Non-incendive CL I-II-III, Div 2, Grp A-B-C-D-E-F-G
Explosion-proof CL I-II-III, Div 1, Grp B-C-D-E-F-G
CSA
Intrinsically safe; Enclosure 4X; T4, max. 85°C
CL I, Div. 1, Grp. A-B-C-D
CL II, Div. 1, Grp. E-F-G
CL III, Div. 1
Non-incendive; Enclosure 4X, max. 85°C
CL I, Div. 2, Grp. A-B-C-D
CL II, Div. 2, Grp. E-F-G
CL III
!
WARNING
The values indicated here have been taken out of the respective approval
certificates. The specifications and supplements according to the certificates
(see chapter “Certificates”) are binding and must be observed.