The table shows the maximum line conductor length in relation to the
section of the conductor itself:
Line conductor cross section (mm²) Line conductor maximum length (m)
4 8 m
6 22 m
10 20 m
16 30 m
The values are calculated in nominal power conditions, considering:
- loss of power along the line no greater than 1%
- use of copper cable, with HEPR rubber insulation and positioned in open air
oad protection switch (AC disconnect switch)
To protect the inverter and the AC connection line, a device must be in-
stalled to protect against maximum current and leakage to ground, with
the following characteristics:
UNO-DM-6.0-TL-PLUS
Type Automatic circuit breaker with differential thermal-magnetic protection
Voltage rating 230 Vac
Current rating 40 A
Magnetic protection characteristic B/C
Differential protection type A/AC
Differential sensitivity 300 mA
Number of poles 2