EasyManua.ls Logo

ABB Zenith ZTS T Series - Page 112

ABB Zenith ZTS T Series
130 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
112
ZENITH ZTS(D) T-SERIES 1600-3000 A & ZTSCT T-SERIES 100-3000 A
Lifting Guidelines for Enclosed Auto-
matic Transfer Switches
1. ABB Zenith automatic transfer switches
are mounted onto a wooden pallet using
bolts and nuts. Please remove the bolts
and nuts prior to lifting.
2. ABB Zenith Automatic Transfer Switch
enclosures have the provisions for lifting
through the standard overhead lifting
device.
3. Position the lifting device across the
top of the enclosure. Engage the lifting
hooks and adjust lifting positions such
that the hooks are pointing outward.
Lifting eyelets
Fig. 9.1 Automatic Transfer Switch Enclosed Assembly
Lifting locations
Note: When lifting the switch using a spreader bar,
height H must be equal to half of distance D
Fig. 9.2 Recommended Lifting Angle
4. Refer to the dimensional drawing for

weight information, lifting provision, and
anchoring hole pattern on lower mount
C-channels.
5. While lifting the unit using lifting
chains, it is recommended to maintain a
45° angle as shown in Fig. 9.2.
6. Refer to Fig. 9.1 for lifting provisions on
the enclosure top.
7. ABB Zenith Automatic Transfer Switch
units should be lifted using propely-rated
lifting devices.
45°
Spreader bar
Lifting eyes
Cabinet
H
D

Other manuals for ABB Zenith ZTS T Series

Related product manuals