2.6.1 Automatic configuration
Basic system parameters can be automat-
ically configured from the HMI: rated volt-
age, rated frequency, each supply power
distribution system type, and neutral
location will be recognized and set by
the controller. Other parameters are
set to factory values; see Chapter 4,
Navigating menu.
2.6.2 In-phase monitor
In-phase monitor is a feature that calcu-
ates the phase difference of supply lines,
preventing transfer when sources are not
in sync. The user can set On/Off from the
HMI. When the in-phase monitor is set to
On, the device measures and detects
when both sources are in sync with each
other. The ATS will allow transfer from
SOURCE 1 (S1) to SOURCE 2 (S2) only when
they are in sync with each other. Any of
these conditions will prevent source
transfer when In-phase monitor is set
to On:
Phase difference between sources
remains greater than 5 degrees
Phase order between sources is not
the same
Voltage amplitude is out of range
Phase is missing
Voltage is asymmetric
Frequency is out of range
S1 and S2 contacts are not paralleled
(Closed transition only)
2.6.3 Powering supply scenarios
Device can be powered by the the follow-
ing methods:
Direct from SOURCE 1 or SOURCE 2:
Controller and HMI are powered and ATS
can be operated electrically.

Controller and HMI are powered, but
load transfer cannot be performed.
Programming port on HMI (USB port):
Only the main board is powered. Allows
software update to main device and
connection of Ekip Connect commis-
sioning tool.