OPERATION, MAINTENANCE, AND INSTALLATION GUIDE
—
6.2 Warnings
LCD
Touch
Message (continued) Fault Action
Local bus Communication between HMI and
switch controller is off
Check connection
Ethernet
disconnected
Ethernet module not connected Check connection
Fire Fighting Fire fighting input activated
Alarm is active and disables transfer
operations as long as the input is active
Control Voltage
Failure
Control voltage dropped during switch
control
Check power source
Control Voltage Low Switch control voltage is below the
minimum
Check power source
Configuration Error Invalid configuration Check parameter values
IEC 61850 Error IEC 61850 failure Check configuration file
Ekip Com Hub Alarm Ekip Com Hub failure Check configuration
HMI Not Compatible
Firmware versions of HMI and device
are not compatible to be used together
Check current versions and update
compatible versions
Table 6.1 Alarms-list in level 3 and 4, LCD and touch control interfaces
Message Reason
S1 and S2 not in sync Voltage sources are not synchronized
Voltage Not Calibrated Calibration data in power module is invalid or unavailable
Current Not Calibrated Calibration data in current measurement module is invalid or unavailable
Pole temperature warning Measured pole temperature is near the alarm level
Control Retry Failed transfer sequence retry activated
Auto Control Disabled Device is in manual operating mode
Local Bus Module heartbeat error.
Check connection. Can be cleared using "Alarm Reset".
Configuration Configuration session ports are open
Clock capacitor charging Real time clock is not yet operational, date & time setting is disabled as
long as this warning is active. Clock capacitor is charged from source
voltage (not AUX) and takes about 10 minutes
—
Table 6.2 Warnings-list in level 3 and 4, LCD and touch control interfaces