EasyManua.ls Logo

Ablerex ARES RT-3K - 4.3.2.2 Cold Start (DC start)

Default Icon
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
39
MODEL
ITEM
ARES
RT-1K
ARES
RT-2K
ARES
RT-3K
CAPACITY
VA
1000 VA 2000 VA 3000 VA
W
when input voltage is 180~300Vac PF=0.9 (900/ 1800/ 2700W)
INPUT
Voltage Rating
110/150/180~300
VAC
(Based on load percentage0 ~ 60% / 0 ~ 75% / 0 ~
100%)
Frequency Rating
45-65
Hz
Phase
Single phase with ground
Power Factor
≧
0.99 (with full linear load)
Generator Input
Supported
Input Connection
10
A,
IEC
320-C14
10
A,
IEC
320-C14
16
A,
IEC
320-C20
Output
Voltage 230 V, adjustable to 200/208/220/230/240
Voltage Regulation within ±1% until low-battery warning
Frequency
(Synchronized Range)
3 Hz or 1 Hz (selectable)
Frequency
(Battery Mode)
50/60 Hz ±0.2% unless synchronized to line
Current Crest Ratio
3:1
Harmonic Distortion
< 3% at full linear
load
< 7% at full non-linear
load
Output Waveform Pure sine
wave
Outlets
(3) 10 A,
IEC 320-C13
(6) 10 A,
IEC 320-C13
(6) 10A,
IEC
320-C13
+
(1) 16A
IEC
320-C19
Overload Capacity
(tolerance
±
1%
)
Line Mode:
<
105%continuous
106-120% for 30 seconds transfer to bypass.
121-150% for 10 seconds transfer to bypass.
>
150
%
Immediately transfer to bypass.
Buzzer continuously alarms.
Battery Mode :
<
105
%
continuous
106-120
%
for 30 seconds shuts down
121-150
%
for 10 seconds shuts down
>
150
%
Immediately shuts down.
Buzzer continuously alarms.
8.4 SNMP Cards
8.4.1 Megatec SNMP card
8.4.1.1 For installation please refer to the user’s manual that came with the card.
8.4.1.2 Installation Position: Optional slot on rear panel
8.4.2 USB
The USB communication protocol definition is as below.
1. Complies with USB version 1.0, 1.5 Mbps.
2. Complies with USB HID version 1.0.
3. Pin Assignments:
9. Specifications Convertible Type (Rack / Tower)
1 Æ VCC (+5V)
2 Æ D-
3 Æ D+
4 Æ Ground