Note:Once the battery is disconnected, the loads are not protected
from power outages.
1. Use an insulated philip screwdriver to remove the four screws located
at the base of the UPS.
2. Remove the front panel and top cover.
3. Use an insulated philip screwdriver to remove the two screws from the
battery holding plate. (for 1500L/1800L/2200L only)
4. Disconnect the battery cable terminals before removing the battery from
the UPS.
Step1: Loosen the black cable from the negative (-) terminal.
Step2: Loosen the red cable from thepositive (+) terminal.
5. Connect the battery cables to the terminals of thenew battery.
Step1: Insert the black cable to the negative (-) terminal.
Step2: Insert the red cable to thepositive (+) terminal.
Note: Small sparks at the battery connectors are normal during connection.
6. Slide the battery into the UPS.
7. Use an insulated philip screwdriver to fasten the two screws on the battery holding plate. (for 1500L/1800L/2200L
only)
8. Close the front panel and fasten the four screws located at the base of the UPS.
9. Dispose off the old battery properly at an appropriate recycling facility.
Refer to the steps below should the UPS fail to
function correctly
Step 1: Is the AC Mains switch in the “ON”
position?
Step 2:Is the UPS plugged into the AC power
supply?
Step 3: Is the power supply within specified unit
values?
Step 4: Has the fuse gone in the mains plug?
Step 5: Is the UPS overload?
Step 6: Is the battery flat or defective?
Problem / Possible Causes
No LEDs display on the front panel.
Charge the UPS at least 6 hours.
Replace the battery with the same capacity.
The UPS is not turned on.
Press the power switch again to turn on the UPS.
Alarm beeps continuously when
the Utility is normal.
Remove some loads/equipment first. The connected equipment exceeds the
UPS specified ‘capacity/load”.
UPS does not provide
expected backup time.
Remove some loads/equipment first. The connected equipment exceeds the
UPS specified ‘capacity/load”.
Battery voltage is too low.
Charge the UPS at least6 hours.
Replace the battery with the same capacity.
The Utility is normal but LED
is flashing.
Reconnect the power cord properly.
Ablerex GR600/GR800 SPECIFICATIONS
Ablerex GR1200/GR1800/GR2000 SPECIFICATIONS
Typical 2-6ms, 10 ms max.
4-6 hours recover to 90% capacity
Packaging Dimension
(WxHxD,mm)
0-90 % RH @ 0-40 C (non-condensing)